Specifications

Project No. 100290066SAT-002A December 30, 2010
Wenzhou Atlantic Import & Export Co., Ltd.
Page 6 of 9
VI. TEST RESULTS & OBSERVATIONS
The test results, computed on the basis of observed flame front advance and
electronic smoke density measurements are presented in the following table.
Test Specimen Flame Spread
Index
Smoke Developed
Index
Design No.:#28 0 40
The data sheets are included in Appendix A. These sheets are actual print-outs of the
computerized data system which monitors the tunnel furnace, and contain all
calibration and specimen data needed to calculate the test results.
VII. OBSERVATIONS
During the test, the specimen was observed to behave in the following manner.
Time
(min:sec)
Observations
0:02 Sagging was observed.
0:04 A steady ignition was observed.
0:06 Melting was observed.
0:11 Flaming drops were observed.
0:12 Floor flames were observed.
After the test, the specimen was observed to be damaged as follows:
Distance
(FEET)
Damage Descriptions
0 - 24
The sample was melted and on the tunnel floor.