Product Manual

55
EN-US
Technical Data
Fronius Symo 10.0-3 208-240 12.0-3 208-240
Input Data
MPP voltage range 300–500 V DC
Input voltage range (at 1000 W/m² / 14°F in an open circuit) 200–600 V DC
Max. input current (MPP1/MPP2)
(MPP1 + MPP2)
25.0/16.5 A
41.5 A
Max. short circuit current of solar modules (I
SC PV
) (MPP1/MPP2) 37.5/24.8 A
Max. recovery current
4)
37.5/24.8 A (RMS)
5)
Output Data
Nominal output power (P
nom
) 9995 W 11995 W
Max. output power (+104°F) 9995 W 11995 W
Max. output power (+122°F)
at 208 V 9800 W 9800 W
at 220 V 9995 W 11300 W
at 240 V 9995 W 11300 W
Phases 3 ~ NPE
Nominal grid voltage
at 208 V 120/208 V
at 220 V 127/220 V
at 240 V 120/240 V
Operating range AC voltage -12 +10%
Grid voltage setting range 60–152 V; 104–288 V
Nominal output current
at 208 V 27.8 A 33.3 A
at 220 V 26.2 A 31.5 A
at 240 V 24.1 A 28.9 A
Maximum output current
at 208 V 31.5 A 35.0 A
at 220 V 29.8 A 35.0 A
at 240 V 27.4 A 32.8 A
Max. output residual current per duration 64 A/2.34 ms
Nominal frequency 50/60 Hz
1)
Total harmonic distortion < 1.5% < 1.75%
Power factor (cos phi) 0 - 1 ind./cap.
2)
General Data
Maximum efficiency 97.00%
CEC efficiency
at 208 V 96.50% 96.50%
at 220 V
at 240 V 96.50% 96.50%
Cooling Controlled forced-air ventilation
Protection class NEMA 4X
Dimensions h x w x d
28.5 x 20.1 x 8.9 in.
725 x 510 x 225 mm
Weight (full/lite version) 91.9 / 91.3 lbs. (41.7 / 41.3 kg)
Permissible ambient temperature -40°F to +140°F (-40°C to +60°C)