Installation Manual

34
Setup 50HN Trip Limit 240V Setup 50HN Trip Limit NL-Mon 240N
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 120 0.16
8
120 0.16
8
50 U < 88 % 211 2
100
211 2
100
110 < U < 120 % 264 1
50
264 1
50
U 120 % 288 0.16
8
288 0.16
8
U
Imin
adjustable
U
Omin
adjustable
120 - 252 0.020 - 21.0
1 - 1050
120 - 252 0.020 - 21.0
1 - 1050
U
Imax
adjustable
U
Omax
adjustable
251 - 322 0.020 - 21.0
1 - 1050
251 - 322 0.016 - 21.0
1 - 1050
Frequency 60 Hz (for all setups) Frequency 50 Hz (for all setups)
F [Hz] Clearing Time [s]
Clearing Time [cyl]
F [Hz] Clearing Time [s]
Clearing Time [cyl]
F
Imax
+ 0.5 > 60.5 0.16
9
F
Imax
+ 0.5
> 50.5 0.16
8
F
Omax
+ 2.0 > 62.0 0.16
9
F
Omax
+ 2.0
> 55.0 0.16
8
F
Imin
- 0.7 < 59.3 0.16
9
F
Imin
- 2.0
< 48.0 0.16
8
F
Omin
- 3.0 < 57.0 0.16
9
F
Omin
- 5.0
< 45.0 0.16
8
F
Imin
adjustable
F
Omin
adjustable
55.0 -
65.0
0.016 - 600
1 - 36000
45.0 -
55.0
0.020 - 600
1 - 30000
F
Imax
adjustable
F
Omax
55.0 -
65.0
0.016 - 600
1 - 36000
45.0 -
55.0
0.020 - 600
1 - 30000
Accuracy 60 Hz 50 Hz
Voltage trip limit accuracy +/- 1.0 % of U
nom
+/- 1.0 % of U
nom
Frequency trip limit accuracy +/- 0.05 Hz +/- 0.05 Hz
Trip time accuracy +/- 16.7 ms (1 cycle) +/- 20 ms (1 cycle)
Detection time 25 ms (1.5 cycles) 30 ms (1.5 cycles)
Reconnection 60 Hz 50 Hz
Reconnection Time 300 s 300 s
Reconnection Time adjustable 5 - 900 s 5 - 900 s
F
max
reconnect value 60 Hz 48 Hz
F
min
reconnect value 60 Hz 50,5 Hz
U
min
reconnect value U > 88 % U > 88 %
U
max
reconnect value U < 106 % U < 106 %
F reconnect value adjustable 55.0 - 65.0 Hz 45.0 - 55.0 Hz
U
min
reconnect value adjustable U > 50 % - U > 99 % U > 50 % - U > 99 %
U
max
reconnect value adjustable U < 101% - U < 120% U < 101% - U < 120%