Product Manual

33
EN-US
Energy Manager
(in Relay Menu
Item)
The "Energy Manager" function can be used to trigger the potential-free switch contact so
that it functions as an actuator.
A user connected to the potential-free switch contact can thus be controlled by assigning
a power feed dependent switch-on or switch-off point.
The potential-free switch contact is switched off automatically:
- When no current is being fed into the public grid supply by the inverter
- When the inverter is switched manually to standby mode
- When there is an effective power assignment of 10% of the power rating
- When there is insufficient solar radiation
Relay Mode
For selection of the various functions of the potential-free switching contact in the data
communications area:
- Alarm function
- Active output
- Energy manager
Setting range ALL / Permanent / OFF / ON / E-manager
Factory setting ALL
Alarm function:
Permanent /
ALL:
Switches the potential-free switching contacts for continual and tem-
porary service codes (e.g., brief interruption of grid power feed opera-
tion, a service code occurs a set number of times per day – can be set
in the "BASIC" menu)
Active output:
ON: The potential-free switching contact NO is switched on at all times
while the inverter is operating (as long as the display lights up or ap-
pears)
OFF: The potential-free switching contact NO is switched off
Energy manager:
E-manager: You can find additional information on the "Energy manager" function
in the "Energy Manager" section below
Relay test
Functional test to check if the potential-free switching contact works
Switch on point (only if "Energy manager" function is activated )
for setting the effective power limit from which the potential-free switching contact will be
switched on
Factory setting 1000 W
Setting range Switch off point – max. power rating of the inverter / W / kW
Switch off point (only if the "Energy manager" function is activated)
for setting the effective power limit from which the potential-free switching contact will be
switched off
Factory setting 500
Setting range 0 – switch on point / W / kW