Product Manual

50
*) If status code persists: Contact a Fronius-trained service technician
**) If this status code keeps recurring, contact your system installer
Class 5 Status
Codes
Class 5 status codes generally do not impair grid power feed operation, but can lead to lim-
itations. They will be displayed until the status code is acknowledged by pressing a key (the
inverter, however, continues working normally in the background).
458 Error during measuring signal detection
Inverter does not feed ener-
gy into the grid.
*)
459 Error during measuring signal detection
for insulation test
460 Reference power source for the digital
signal processor (DSP) is operating out-
side of tolerances
461 Error in DSP data memory
462 Error in DC feed-in monitoring routine
463 AC polarity reversed, AC connector
plugged in incorrectly
474 RCMU sensor faulty
Inverter does not feed ener-
gy into the grid.
**)
475 Insulation error (connection between so-
lar module and ground)
476 Supply voltage for driver too low
480 -
481
Function incompatibility (one or more PC
boards in the inverter are not compatible
with each other, e.g., after PC board re-
placement)
Inverter does not feed ener-
gy into the grid.
Update inverter firm-
ware; *)
482 Setup interrupted after initial commis-
sioning Inverter does not feed ener-
gy into the grid.
Restart setup after AC
reset (switch automatic
circuit breaker off and
on)
483 Voltage U
DCfix
for MPP2 string is outside
of valid range
Inverter does not feed ener-
gy into the grid.
Check MPP settings; *)
485 CAN transmission buffer is full
Inverter does not feed ener-
gy into the grid.
Carry out AC reset
(switch automatic circuit
breaker off and on); *)
Code Description Behavior Remedy
Code Description Behavior Remedy
502 Insulation fault on solar mod-
ules
Warning message is
shown on the display
**)
509
No feed-in within the last 24
hours
Warning message is
shown on the display
Acknowledge status code;
Check whether all conditions for
problem-free grid power feed opera-
tion are met (e.g., whether solar mod-
ules are covered with snow); **)
515 No internal communication
with filter
Warning message on
the display
*)
516 Communication with memory
unit not possible
Warning message of
memory unit
*)