Datasheet

1kVA / 2kVA / 3kVA
Champ Series
© 2017 FSP Group. All Rights Reserved. All trademarks are registered to their respective owners.
Specifications
MODEL
CAPACITY
INPUT
Voltage
Frequency Range
Power Factor
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion (THDv)
Waveform (Batt. Mode)
EFFICIENCY
Line Mode
Battery Mode
Champ 1K
1000 VA / 900 W
88%
83%
Champ 2K
2000 VA / 1800 W
200/208/220/230/240Vac
180Vac / 160Vac / 140Vac / 120Vac ± 5%
(based on load percentage 100%-80% / 80%-70% / 70-60% / 60%-0)
195Vac / 175Vac /
155V
ac
/ 135V
ac
± 5%
(based on load percentage 100%-80% / 80%-70% / 70-60% / 60%-0)
300Vac / 280Vac ± 5%
(based on load percentage 0-80% / 80%-100%)
290VAC / 270VAC ± 5%
(based on load percentage 0-80% / 80%-100%)
40Hz ~ 70 Hz
0.99 @ Nominal Voltage (100% load)
200/208/220/230/240Vac
± 1%
47~ 53 Hz or 57 ~ 63 Hz
50 Hz or 60Hz ± 0.5%
3:1
3 % THD (Linear Load)
6 % THD (Non-linear Load)
Zero
4 ms (Typical)
Pure Sinewave
89%
85%
Champ 3K
3000 VA / 2700 W
90%
88%
Voltage
Range
Low Line Transfer
Low Line Comeback
High Line Transfer
High Line Comeback
Transfer
Time
Line Mode to Battery
Inverter to Bypass