Step3 Click“Apply”buttontosavethesettings. Eachfunctionsettingissavedby
clickingeach“Apply”button.
NOTE1:AnyfunctionswhicharenotsupportedbyUPSwillnotbeabletoaccess.
NOTE2:Click“Default”buttontorecoverthedefaultsetting.
l UPSalarm:Ifenabled,UPSalarmwillbeactivated.Viceversa.
l Alarm at bypass mode:If enabled, UPS alarmswhen it’s working at bypass
mode. Viceversa.
l Alarm atbatterymode: If disabled,UPS willnot alarm whenit’sworkingat
batterymode.Viceversa.
l Auto reboot: If enabled, UPS will auto recover when AC is recovering. Vice
versa.
l BypasswhenUPSisoff:Ifenabled,ACwilldirectlyprovidepowertoconnected
deviceswhenUPSisoff.Viceversa.
l Convertermode:Ifenabled,theUPSwill operateinconvertermode.Viceversa.
l ECOmode:Ifenabled,theUPSwilloperateinECOmodewheninputvoltageis
withinacceptablerange.Viceversa.
l Battery open status check: If enabled, the monitored UPS will check if the
batteryconnectionokornotwhenUPSisturnedon.
l Coldstart: If disabled, the UPScanbeturned on onlywhenAC is normally
connectedtoUPS.Viceversa.
l Bypassnotallowed:Ifenabled,theUPSwillnottransfertobypassmodeunder
anyconditions. Ifdisabled,theUPSwillbeallowedtotransfertobypassmode
accordingtoUPSinternalsetting.
l Batterydeepdischargeprotection:Ifenabled,themonitoredUPSshutdownin
accordancewiththeconditionofbatteryandloadonbatterymodetoprotect
battery.Viceversa.
l Sitefaultdetection: Ifenabled,themonitoredUPSwillbeepwhentheinput
neutralandhotwiresarereversed.Viceversa.
l P1 Programmable outlet control (battery mode): If enabled, when UPS is
runningatbatterymode,it will cutoffP1outlets afterbackup setting time arrive.