User manual
6. Trouble Shooting
Use the table below to solve minor problems.
Problem Possible Cause Solutions
Low battery Charge the UPS at least 6 hours.
Battery fault
Replace the battery with the same type of
battery.
LED display on the front
panel does not work.
The UPS is not turned on. Press the power switch again to turn on
the UPS.
Alarm continuously
sounds when the
mains is normal.
The UPS is overload. Remove some loads first. Before
reconnecting equipment, please verify
that the load matches the UPS capability
specified in the specs.
The UPS is overload. Remove some critical load. Entfernen Sie
nicht notwendige Spannungsgeräte.
Battery voltage is too low. Charge the UPS at least 6 hours.
When power fails,
back-up time is shorten.
Battery defect. It might be due to
high temperature operation
environment, or improper
operation to battery.
Replace the battery with the same type of
battery.
The mains is normal
Bu the unit is on
battery mode.
Power cord is loose. Reconnect the power cord properly.
7 Specifications
Model EP 1000
CAPACITY 1000 VA / 600 W
INPUT
Voltage 110/120 VAC or 220/230/240 VAC
Voltage Range 81-145 VAC / 162-290 VAC
OUTPUT
Voltage Regulation +/-10%
Transfer Time Typical 2-6 ms, 10 ms max.
Waveform Simulated Sine Wave
BATTERY
Type & Number 12 V/7 AH x 2
Charging Time 4-6 hours recover to 90% capacity
PHYSICAL
Dimension (DxWxH) 350 x 146 x 160 mm
Net Weight (kgs) 8.0
Environment
Humidity
0-90 % RH @ 0-40° C (non-condensing)
Noise Level Less than 40 dB
MANAGEMENT
USB/RS-232 (Option) Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux,
Unix, and MAC
1. Lieferumfang
Im Lieferumfang sollten Sie folgendes finden:
- USV Einheit
- Kurzanleitung
- Kommunikationskabel (nur für Modelle mit USB/RS-232 Schnittstelle)
- Netzkabel (nur für Modelle mit IEC-Eingang)
2. Produktübersicht
Vorderansicht:
Rückansicht:
Line Interactive UPS
Quick Guide V.2.0
Ausgänge
AC Eingang
Schutzschalter
Modem / Telefon /
Netzwerk Überspannungsschutz
RS-232 com. Schnittstelle
USB com. Schnittstelle
4 5
Ein/Aus Schalter
Betriebsanzeige: grün
Batteriemodus: gelb blinkend
Fehlermeldung: rot
DE