Home Theater Screen User Manual

2 - 65
23
23 YASKAWA PLC 2
YASKAWA PLC • 2
(CP9200SH/MP900)
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Available Memory
When setting the MB/IB memories , set the bit number by HEX .
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
Memobus port
on a CPU module
PLC Link Unit
RS-232C [Wiring Diagram 1]
Select PLC Type
CP9200SH
/MP900
CP9200SH
MP920,
MP930
CP-217IF
217IF
RS-232C [Wiring Diagram 1]
[Wiring Diagram 2]
RS-422 [Wiring Diagram 3]
RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 4]
Wiring Diagram
19200bps
Even
1
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 1
Port
Error Check
Item Setting of PLC
19200bps
Even
1
Port Delay Timer
1
0 (fixed)
CRC (fixed)
8
Comm. Parameter of POD
8
MBxxxx
DEC
Bit No. : HEX
Memory TYPE Remarks
MW (word device) 0
IW (input register) 1 Read only
MB (coil) 4
IB (input coil) 6 Read only