Home Theater Screen User Manual

2 - 14
FUJI PLC • 6
(TOYOTA version NJ Computer Link)
6
Port 0
19200bps
Even
7
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
Item Setting of PLC
0
19200bps
Even
7
11
Comm. Parameter of POD
*
1
*
1
PLC
Computer link
of FLEX-PC NJ-JM
RS-422 [Wiring Diagram 1]
Select PLC Type
FLEX-PC
COM
Wiring Diagram
Available PLC
Connect to the terminal block of the NJ-JM computer link.
For further information, refer to the PLC manual.
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
*
1 The station No. other than zero (0) is invalid for communication.
PLC Setting
It is necessary to set the computer link parameters in the file register on the PLC.
For the communication parameters above, set “0026h” into W0000 in the file register to define the OPDF
command.
5 FUJI PLC 6