Auxiliary heater control 1
Operation Condition
Heater on Heater is on as shown in following diagram of heating temperature.
Heater off
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
All control temperatures will shift by adjusting “Thon”.
Off
Off
On
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts
Tr-Ts (=Thon) < -5.4°F
(
-3°C)
Tr-Ts ≥ -18°F
(-10°C
Tr-Ts < -21.6°F (-12°C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Example: When set temperature (Ts) is 72°F (22°C) (Factory setting),
and room temperature (Tr) increases above 53.6°F (12°C), signal output is on.
and room temperature (Tr) increases above 69.8°F (21°C), signal output is off.
and room temperature (Tr) decreases below 66.2°F (19°C), signal output is on.
and room temperature (Tr) decreases below 50°F (10°C), signal output is off.
Auxiliary heater control 2
Operation Condition
Heater on Heater is on as shown in following diagram of heating temperature.
Heater off
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
All control temperatures will shift by adjusting “Thon”.
Off
On
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts
Tr-Ts (=Thon) < -5.4°F
(
-3°C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
- 26 -
8-4. Details of function 8. External input and output
WALL MOUNTED
ASUG09-12LMAS
WALL MOUNTED
ASUG09-12LMAS