Multiple outdoor unit installation
Provide at least 250 mm of space between the outdoor units if multiple units are installed.
When routing the piping from the side of an outdoor unit, provide space for piping.
No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following ex-
ample “When an obstruction in the upper space:”.
When the upper space is open:
Unit: in (mm)
Obstacles at rear only Obstacles at front only
10 (250) or more
8 (200)
or more
10 (250) or mo
r
e
40 (1,000)
or more
Obstacles at front and rear
10 (250) or more
8 (200) or more
40 (1,000) or more
When an obstruction in the upper space:
Unit: in (mm)
Obstacles at rear and above.
10 (250)
or more
10 (250)
or more
60 (1,500)
or more
60 (1,500)
or more
8 (200) or more
Max. 11 (300)
- 51 -
3-1. Models: AOUG09LMAS1 and AOUG12LMAS1 3. Installation space
OUTDOOR UNIT
AOUG09-12LMAS1
OUTDOOR UNIT
AOUG09-12LMAS1