Design and Technical Manual

Table Of Contents
7. Additional charge calculation
7-1. Model: AOUG09LMAS1
Refrigerant type R410A
Refrigerant amount
lb oz 2 lb 2 oz
g 950
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.22 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge
oz 0 3.5
g 0 100
7-2. Model: AOUG12LMAS1
Refrigerant type R410A
Refrigerant amount
lb oz 2 lb 3 oz
g 1,000
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.22 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge
oz 0 3.5
g 0 100
- 56 -
7-1. Model: AOUG09LMAS1 7. Additional charge calculation
OUTDOOR UNIT
AOUG09-12LMAS1
OUTDOOR UNIT
AOUG09-12LMAS1