Service Manual
Table Of Contents
- SERVICE MANUAL
- 1. GENERAL INFORMATION
- 2. TECHNICAL DATA AND PARTS LIST
- 3. TROUBLESHOOTING
- 1. Error code
- 2. Troubleshooting with error code
- 2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- 2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- 2-3. E: 12. Wired remote controller communication error (Indoor unit)
- 2-4. E: 18. External communication error (Indoor unit)
- 2-5. E: 32. Indoor unit main PCB error (Indoor unit)
- 2-6. E: 35. MANUAL AUTO button error (Indoor unit)
- 2-7. E: 41. Room temperature sensor error (Indoor unit)
- 2-8. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
- 2-9. E: 51. Indoor unit fan motor error (Indoor unit)
- 2-10. E: 58. Intake grille error (Indoor unit)
- 2-11. E: 62. Outdoor unit main PCB error (Outdoor unit)
- 2-12. E: 63. Inverter error (Outdoor unit)
- 2-13. E: 64. PFC circuit error (Outdoor unit)
- 2-14. E: 71. Discharge thermistor error (Outdoor unit)
- 2-15. E: 73. Outdoor unit heat exchanger thermistor error (Outdoor unit)
- 2-16. E: 74. Outdoor temperature thermistor error (Outdoor unit)
- 2-17. E: 84. Current sensor error (Outdoor unit)
- 2-18. E: 94. Trip detection (Outdoor unit)
- 2-19. E: 95. Compressor motor control error (Outdoor unit)
- 2-20. E: 97. Outdoor unit fan motor error (Outdoor unit)
- 2-21. E: 99. 4-way valve error (Outdoor unit)
- 2-22. E: A1. Discharge temperature error (Outdoor unit)
- 3. Troubleshooting without error code
- 4. Troubleshooting with error code (For wireless LAN adapter)
- 4-1. E: 18. External communication error between indoor unit and WLAN adapter
- 4-2. Wireless LAN adapter error
- 4-3. Network communication error between wireless LAN router and WLAN adapter
- 4-4. E: 18. Communication error
- 4-5. E: 18. Wireless LAN adapter non-energized
- 4-6. Wireless LAN adapter Sleep mode (Indoor unit)
- 4-7. Mobile app setting method
- 5. Service parts information
- 6. Thermistor resistance values
- 4. CONTROL AND FUNCTIONS
- 1. Compressor frequency control
- 2. Auto changeover operation
- 3. Fan control
- 4. Louver control
- 5. Timer operation control
- 6. Defrost operation control
- 7. Various control
- 7-1. Auto restart
- 7-2. MANUAL AUTO operation
- 7-3. Forced cooling operation
- 7-4. 10 °C HEAT operation
- 7-5. ECONOMY operation
- 7-6. POWERFUL operation
- 7-7. Compressor preheating
- 7-8. Electronic expansion valve control
- 7-9. Prevention to restart for 3 minutes (3 minutes st)
- 7-10. 4-way valve control
- 7-11. Outdoor unit low noise operation
- 8. Various protections
- 5. FILED WORKING
¢ Sleep timer
If the sleep timer is set, the room temperature is monitored and the operation is stopped auto-
matically. If the operation mode or the set temperature is change after the sleep timer is set, the
operation is continued according to the changed setting of the sleep timer from that time on.
• In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting
temperature another 1°C after 1 hour. After that, the setting temperature is not changed and
the operation is stopped at the setting time.
Set temperature rises
Ts: Set temperature
Stop of operation
Ts
+2°C
Set 60 min
+1°C
• In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting
temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not
changed and the operation is stopped at the setting time.
Set
Ts
-2°C
-1°C
-3°C
-4°C
Ts: Set temperature
30 min 30 min
30 min
Stop of operation
Set temperature rises
¢ Weekly timer
On and off timer can be combined, and up to 4 reservations per day and 28 reservations per
week. Before setting the program, set the week and time of the air conditioner at first. If the week
and time are not set, the weekly timer will not operate correctly at the setting time.
5-2. Wired remote control
- (04-21) - 5. Timer operation control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS