Service Manual
Table Of Contents
- SERVICE MANUAL
- 1. GENERAL INFORMATION
- 2. TECHNICAL DATA AND PARTS LIST
- 3. TROUBLESHOOTING
- 1. Error code
- 2. Troubleshooting with error code
- 2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- 2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- 2-3. E: 12. Wired remote controller communication error (Indoor unit)
- 2-4. E: 18. External communication error (Indoor unit)
- 2-5. E: 32. Indoor unit main PCB error (Indoor unit)
- 2-6. E: 35. MANUAL AUTO button error (Indoor unit)
- 2-7. E: 41. Room temperature sensor error (Indoor unit)
- 2-8. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
- 2-9. E: 51. Indoor unit fan motor error (Indoor unit)
- 2-10. E: 58. Intake grille error (Indoor unit)
- 2-11. E: 62. Outdoor unit main PCB error (Outdoor unit)
- 2-12. E: 63. Inverter error (Outdoor unit)
- 2-13. E: 64. PFC circuit error (Outdoor unit)
- 2-14. E: 71. Discharge thermistor error (Outdoor unit)
- 2-15. E: 73. Outdoor unit heat exchanger thermistor error (Outdoor unit)
- 2-16. E: 74. Outdoor temperature thermistor error (Outdoor unit)
- 2-17. E: 84. Current sensor error (Outdoor unit)
- 2-18. E: 94. Trip detection (Outdoor unit)
- 2-19. E: 95. Compressor motor control error (Outdoor unit)
- 2-20. E: 97. Outdoor unit fan motor error (Outdoor unit)
- 2-21. E: 99. 4-way valve error (Outdoor unit)
- 2-22. E: A1. Discharge temperature error (Outdoor unit)
- 3. Troubleshooting without error code
- 4. Troubleshooting with error code (For wireless LAN adapter)
- 4-1. E: 18. External communication error between indoor unit and WLAN adapter
- 4-2. Wireless LAN adapter error
- 4-3. Network communication error between wireless LAN router and WLAN adapter
- 4-4. E: 18. Communication error
- 4-5. E: 18. Wireless LAN adapter non-energized
- 4-6. Wireless LAN adapter Sleep mode (Indoor unit)
- 4-7. Mobile app setting method
- 5. Service parts information
- 6. Thermistor resistance values
- 4. CONTROL AND FUNCTIONS
- 1. Compressor frequency control
- 2. Auto changeover operation
- 3. Fan control
- 4. Louver control
- 5. Timer operation control
- 6. Defrost operation control
- 7. Various control
- 7-1. Auto restart
- 7-2. MANUAL AUTO operation
- 7-3. Forced cooling operation
- 7-4. 10 °C HEAT operation
- 7-5. ECONOMY operation
- 7-6. POWERFUL operation
- 7-7. Compressor preheating
- 7-8. Electronic expansion valve control
- 7-9. Prevention to restart for 3 minutes (3 minutes st)
- 7-10. 4-way valve control
- 7-11. Outdoor unit low noise operation
- 8. Various protections
- 5. FILED WORKING
• When function setting is “Operation/Stop” mode 2
– In the case of “Edge” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-03 1
External input and
output PCB
CN313
Off → On Operation
On → Off
Stop (R.C.
disabled)
On
CN313
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote contoller
On OnOff
– In the case of “Pulse” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-03 1
External input and
output PCB
CN313 Pulse Operation
CN314 Pulse
Stop (R.C.
disabled)
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
(R.C. disabled)
Off
On
NOTE:
When “Operation/Stop” mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
2-4. Details of function
- (05-17) - 2. External input and output
FIELD
WORKING
FIELD
WORKING