Service Manual
Table Of Contents
- SERVICE MANUAL
- 1. GENERAL INFORMATION
- 2. TECHNICAL DATA AND PARTS LIST
- 3. TROUBLESHOOTING
- 1. Error code
- 2. Troubleshooting with error code
- 2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- 2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- 2-3. E: 12. Wired remote controller communication error (Indoor unit)
- 2-4. E: 18. External communication error (Indoor unit)
- 2-5. E: 32. Indoor unit main PCB error (Indoor unit)
- 2-6. E: 35. MANUAL AUTO button error (Indoor unit)
- 2-7. E: 41. Room temperature sensor error (Indoor unit)
- 2-8. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
- 2-9. E: 51. Indoor unit fan motor error (Indoor unit)
- 2-10. E: 58. Intake grille error (Indoor unit)
- 2-11. E: 62. Outdoor unit main PCB error (Outdoor unit)
- 2-12. E: 63. Inverter error (Outdoor unit)
- 2-13. E: 64. PFC circuit error (Outdoor unit)
- 2-14. E: 71. Discharge thermistor error (Outdoor unit)
- 2-15. E: 73. Outdoor unit heat exchanger thermistor error (Outdoor unit)
- 2-16. E: 74. Outdoor temperature thermistor error (Outdoor unit)
- 2-17. E: 84. Current sensor error (Outdoor unit)
- 2-18. E: 94. Trip detection (Outdoor unit)
- 2-19. E: 95. Compressor motor control error (Outdoor unit)
- 2-20. E: 97. Outdoor unit fan motor error (Outdoor unit)
- 2-21. E: 99. 4-way valve error (Outdoor unit)
- 2-22. E: A1. Discharge temperature error (Outdoor unit)
- 3. Troubleshooting without error code
- 4. Troubleshooting with error code (For wireless LAN adapter)
- 4-1. E: 18. External communication error between indoor unit and WLAN adapter
- 4-2. Wireless LAN adapter error
- 4-3. Network communication error between wireless LAN router and WLAN adapter
- 4-4. E: 18. Communication error
- 4-5. E: 18. Wireless LAN adapter non-energized
- 4-6. Wireless LAN adapter Sleep mode (Indoor unit)
- 4-7. Mobile app setting method
- 5. Service parts information
- 6. Thermistor resistance values
- 4. CONTROL AND FUNCTIONS
- 1. Compressor frequency control
- 2. Auto changeover operation
- 3. Fan control
- 4. Louver control
- 5. Timer operation control
- 6. Defrost operation control
- 7. Various control
- 7-1. Auto restart
- 7-2. MANUAL AUTO operation
- 7-3. Forced cooling operation
- 7-4. 10 °C HEAT operation
- 7-5. ECONOMY operation
- 7-6. POWERFUL operation
- 7-7. Compressor preheating
- 7-8. Electronic expansion valve control
- 7-9. Prevention to restart for 3 minutes (3 minutes st)
- 7-10. 4-way valve control
- 7-11. Outdoor unit low noise operation
- 8. Various protections
- 5. FILED WORKING
Auxiliary heater control by outdoor temperature 1
This control selects heat pump or external heater according to the outdoor temperature. When out-
door temperature is high, the heating is performed by using heat pump only.
Operation Condition
Heater on Heater is on as shown in following diagram of heating temperature.
Heater off
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
• Heat pump only zone
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
• Outdoor temperature zone boundary A and B: Adjustable individually by function setting number
66 and 67.
• External heater output
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts ≥ 0.9°F
(0.5°C)
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F
(
-0.5°C)
• Outdoor temperature zone
Heat pump only zone
(Heat pump)
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
B: 42.8°F (6°C)*
A: -4°F (-20°C)*
B + 3.6°F (2°C): 46.4°F (8°C)
A + 3.6°F ( 2°C): -0.4°F (-18°C)
Outdoor temp.
*: Adjustable by function setting 66 and 67
2-4. Details of function
- (05-24) - 2. External input and output
FIELD
WORKING
FIELD
WORKING