Check point 4. Check serial signal (reverse transfer signal)
Check serial signal (Forward transfer signal)
RED
WHITE
BLACK
BLACK
WHITE
GREEN
+
-
N
L
3
2
1
Check if indicated value swings between AC 30 V and AC 130 V at outdoor unit terminal 2—3.
If it is abnormal, replace main PCB.
If it is abnormal, check indoor unit fan motor. (Indoor unit fan motor in "Service parts informa-
tion" on page 03-64)
If indoor unit fan motor is abnormal, replace indoor unit fan motor and main PCB.
End
Check point 1-2. Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
End