Service Manual
Table Of Contents
- SERVICE MANUAL
- 1. GENERAL INFORMATION
- 2. TECHNICAL DATA AND PARTS LIST
- 3. TROUBLESHOOTING
- 1. Error code
- 2. Troubleshooting with error code
- 2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- 2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- 2-3. E: 12. Wired remote controller communication error (Indoor unit)
- 2-4. E: 18. External communication error (Indoor unit)
- 2-5. E: 32. Indoor unit main PCB error (Indoor unit)
- 2-6. E: 35. MANUAL AUTO button error (Indoor unit)
- 2-7. E: 41. Room temperature sensor error (Indoor unit)
- 2-8. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
- 2-9. E: 51. Indoor unit fan motor error (Indoor unit)
- 2-10. E: 58. Intake grille error (Indoor unit)
- 2-11. E: 62. Outdoor unit main PCB error (Outdoor unit)
- 2-12. E: 63. Inverter error (Outdoor unit)
- 2-13. E: 64. PFC circuit error (Outdoor unit)
- 2-14. E: 71. Discharge thermistor error (Outdoor unit)
- 2-15. E: 73. Outdoor unit heat exchanger thermistor error (Outdoor unit)
- 2-16. E: 74. Outdoor temperature thermistor error (Outdoor unit)
- 2-17. E: 84. Current sensor error (Outdoor unit)
- 2-18. E: 94. Trip detection (Outdoor unit)
- 2-19. E: 95. Compressor motor control error (Outdoor unit)
- 2-20. E: 97. Outdoor unit fan motor error (Outdoor unit)
- 2-21. E: 99. 4-way valve error (Outdoor unit)
- 2-22. E: A1. Discharge temperature error (Outdoor unit)
- 3. Troubleshooting without error code
- 4. Troubleshooting with error code (For wireless LAN adapter)
- 4-1. E: 18. External communication error between indoor unit and WLAN adapter
- 4-2. Wireless LAN adapter error
- 4-3. Network communication error between wireless LAN router and WLAN adapter
- 4-4. E: 18. Communication error
- 4-5. E: 18. Wireless LAN adapter non-energized
- 4-6. Wireless LAN adapter Sleep mode (Indoor unit)
- 4-7. Mobile app setting method
- 5. Service parts information
- 6. Thermistor resistance values
- 4. CONTROL AND FUNCTIONS
- 1. Compressor frequency control
- 2. Auto changeover operation
- 3. Fan control
- 4. Louver control
- 5. Timer operation control
- 6. Defrost operation control
- 7. Various control
- 7-1. Auto restart
- 7-2. MANUAL AUTO operation
- 7-3. Forced cooling operation
- 7-4. 10 °C HEAT operation
- 7-5. ECONOMY operation
- 7-6. POWERFUL operation
- 7-7. Compressor preheating
- 7-8. Electronic expansion valve control
- 7-9. Prevention to restart for 3 minutes (3 minutes st)
- 7-10. 4-way valve control
- 7-11. Outdoor unit low noise operation
- 8. Various protections
- 5. FILED WORKING
2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator Indoor unit
Operation indicator 1 time flash
Timer indicator 2 time flash
Economy indicator Continuous flash
Error code E: 12
Detective actuator
Indoor unit Main PCB When the indoor unit cannot receive the signal from
Wired remote controller more than 1 minute during
normal operation.
Wired remote control
Forecast of cause
Terminal connection abnormal
Wired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the
followings.
• Check the connection of terminal between
remote controller and indoor unit, and check
if there is a disconnection of the cable.
↓
Check point 2. Check connection
• If it is DC 5 V, remote controller is failure.
(Main PCB is normal)
– Replace Remote Control
• If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
– Replace main PCB
Check voltage at CN2 (terminal 1—3)
of UTY-TWRXZ2 (Communication kit).
(Power supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
↓
End
2-3. E: 12. Wired remote controller communication error (Indoor unit) - (03-13) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING