ASUG12LZBS Operation Manual

En-14
State of indicator lamps
: The instruction is relating to the wireless LAN control
(optional).
Lighting pattern: O󰀨, On, Blinking, Any state
State Causes and solutions
See
page
Automatic defrosting operation
Wait until nishing the defrosting
(maximum of 15 minutes).
10
Filter indicator
Clean the air lter and reset the lter
sign.
10
Error code display
Consult authorized service personnel.
-
Timer setting error because of Auto restart
Reset the clock and timer settings.
10
Test run operation (for authorized
personnel only)
Press
to quit the test run.
3
The power to the access point is not
on.
-
Check that the power to the access
point is on.
There is a possibility that the WLAN
adapter is not properly connected to
the access point.
11
Disconnect the power supply to the air
conditioner (via breaker or plug), and
then re-connect.
The software of the WLAN adapter is
being updated.
-
During the air conditioner registration
(pairing of WLAN adapter)
11
Restricted function
11
Manual auto operation and Filter indicator
reset
You can operate the air conditioner with on the
indoor unit.
Status Length of pressing down Mode or operation
In operation More than 3 seconds Stop
Stopping 2 seconds or less Filter indicator reset
More than 3 seconds and
less than 10 seconds
Auto
More than 10 seconds
(Only for servicing.*)
Forced cooling
*:To stop the forced cooling, press this button or
on the remote
controller.
(3 times)
(Fast)
(Slow)