AUU12RLF Installation Manual

En-7
6.1.1. Installing body
Cealing openings and hanging bolt installation diagram
WARNING
When fastening the hangers, make the bolt positions
uniform.
530 (20-7/8) (Hanging bolt position)
540 (21-1/4) (Hanging bolt position)
570(22-7/16) (Indoor unit)
580-660 (22-27/32 - 25-31/32 ) (Cealing openings)
700 (27-9/16) (Decoration Panel)
135 (5-5/16)
250 (9-27/32)
75 (2-15/16)
Drain pipe (O.D. ø26.1) (1-1/32)
40 (1-9/16) 99 (3-29/32)102 (4-1/32)
114 (4-1/2)
215 (8-15/32)
30
(1-3/16)
262 (10-5/16)
30 (1-3/16)
58 (2-9/32)
123 (4-27/32)
Ceiling
Control box
Liquid pipe
Gas pipe
x
Be sure to leave service access for future service at the designated
position.
150-200 (5-29/32 - 7-7/8 )
Min. 450 (17-23/32)
Min. 450 (17-23/32)
Service access
Unit: mm (in.)
Unit: mm (in.)
(1) Install special nut A, then special nut B onto the hanging
bolt.
(2) Raise the body and mount its hooks onto the hanging bolt
between the special nuts.
(3) Turn special nut B to adjust the height of the body.
WARNING
Perform  nal tightening by tightening the double nut
rmly.
Special nut A
Special nut B
Hook
Hanging bolt
30 (1-3/16)
or more
After installing the
body, tighten the nuts.
19 (3/4)
Ceiling
Unit: mm(in.)
6.1.2. Leveling
Using a level, or vinyl hose  lled with water,  ne adjust so that
the body is level.
Vinyl hose
6.1.3. Installing drain pipe
Note: Install the drain pipe.
x
Install the drain pipe with downward gradient (1/50 to
1/100) and so there are no rises or traps in the pipe.
x
Use general hard polyvinyl chloride pipe [3/4 in. (O.D.
1-1/16 in)] and connect it with adhesive (polyvinyl chlo-
ride) so that there is no leakage.
x
When the pipe is long, install supporter.
x
Do not perform air bleeding.
x
Always heat insulate indoor section of drain pipe.
x
When desiring a high drain pipe height, raise it up to 700 mm
(27-9/16 in.) or less from the ceiling within a range of 300 mm
(11-13/16 in.) from the body. A rise dimension over this range
will cause leakage. See  gure on next page.
x
Set up the entire piping lines at the position 100 mm
(3-15/16 in.) lower than the main body drain port, and use
the piping lines O.D. 33 mm (1-5/16 in.) or more with the
descending inclination to 1/100 or more.
b
itions
NG:air bleeding
NG:Rise
NG:trap
Pipe Size
Drain pipe 3/4 in. (O.D. 1-1/16 in.)