LMAS Service Manual

Table Of Contents
5-3. Outdoor unit Electronic Expansion Valve (EEV)
Check point 1. Check connections
Check connection of connector. (Loose connector or open cable)
NOTE: For details of wiring diagram, refer to "→iring diagrams" in Chapter 2. TECHNICAL DATA
AND PARTS LIST on page 02-18.
Check point 2. Check coil of EEV
Remove connector, check each winding resistance of coil.
Read wire Resistance value
1(Red) - 2(Blue)
46 Ω ±3 Ω
at 68 °F (20 °C)
1(Red) - 3(Orange)
1(Red) - 4(↔ellow)
1(Red) - 5(→hite)
 If Resistance value is abnormal, replace EEV.
Check point 3. Check Voltage from main PCB
Remove connector and check voltage (DC 12 V)
 If it does not appear, replace main PCB.
Check point 4. Check noise at start up
Turn on the power and check the operation noise.
 If an abnormal noise does not show, replace main PCB.
Check point 5. Check Opening and Closing Operation of Valve
→hen valve is closed, it has a temp. difference
between inlet and outlet
Pipe (In)
Pipe (Out)
Hi TEMP.
Normal TEMP.
CLOSE
Example : Hot Gas
If it is open, it has no temp. difference between
inlet and outlet
Pipe (In)
Hi TEMP.
OPEN
Example : Hot Gas
Pipe (Out)
Hi TEMP.
5-3. Outdoor unit Electronic Expansion Valve (EEV) - (03-82) - 5. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING