LMAS Service Manual

Table Of Contents
2-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
¢
Indoor unit
A twisted pair cable (22A→G) should be used. Maximum length of cable is 82 ft (25 m).
Output voltage: High DC 12 V ± 2 V, Low 0 V.
Permissible current: 50 mA
For details, refer to
"Combination of external input and output" on page 05-17.
When indicator or other components are connected directly
Example: Function setting 60 is set to "00"
1
2
Connector
(CN47)
LED
PCB
Resistor
Connected unit
+
-
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
1
2
Connected device
Connector
(CN47)
PCBConnected unit
Relay
(Operation status)
-
+
2-2. External output - (05-15) - 2. External input and output
FIELD
WORKING
FIELD
WORKING