2-4. Details of function
¢
Control input function
When function setting is “Operation/Stop” mode 1
In the case of “Edge” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-00 1
External input and
output PCB
CN313
Off  On Operation
On  Off Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
CN313
In the case of “Pulse” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-00 1
External input and
output PCB
CN313 Pulse Operation
CN314 Pulse Stop
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
NOTES:
The last command has priority.
The indoor units within the same remote controller group operates in the same mode.
2-4. Details of function - (05-19) - 2. External input and output