LMAS Service Manual
Table Of Contents
- SERVICE MANUAL
- 1. GENERAL INFORMATION
- 2. TECHNICAL DATA AND PARTS LIST
- 3. TROUBLESHOOTING
- 1. Error code
- 1-1. How to check the error memory
- 1-2. How to erase the error memory
- 1-3. Error code table (Indoor unit and wired remote controller)
- 1-4. Error code table (Outdoor unit)
- 1-5. Error code table (Wireless LAN indicator)
- 1-6. Error code table (Mobile app)
- 1-7. Error message for wireless LAN control (Mobile app)
- 2. Troubleshooting with error code
- 2-1. E: 11.X. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- 2-2. E: 11.X. Serial communication error (Serial forward transfer error) (Indoor unit)
- 2-3. E: 12.X. Wired remote controller communication error (Indoor unit)
- 2-4. E: 18.X. External communication error (Indoor unit)
- 2-5. E: 23.X. Combination error (Outdoor unit)
- 2-6. E: 26.X. Address setting error in wired remote controller (Indoor unit)
- 2-7. E: 29.X. Connected unit number error (Indoor unit)
- 2-8. E: 32.X. Indoor unit main PCB error (Indoor unit)
- 2-9. E: 35.X. MANUAL AUTO button error (Indoor unit)
- 2-10. E: 3A.X. Indoor unit communication circuit error (Indoor unit)
- 2-11. E: 41.X. Room temperature sensor error (Indoor unit)
- 2-12. E: 42.X. Indoor unit heat exchanger sensor error (Indoor unit)
- 2-13. E: 51.X. Indoor unit fan motor error (Indoor unit)
- 2-14. E: 58.X. Intake grille error (Indoor unit)
- 2-15. E: 62.X. Outdoor unit main PCB error (Outdoor unit)
- 2-16. E: 63.X. Inverter error (Outdoor unit)
- 2-17. E: 64.X. PFC circuit error (Outdoor unit)
- 2-18. E: 65.X. Trip terminal L error (Outdoor unit)
- 2-19. E: 71.X. Discharge thermistor error (Outdoor unit)
- 2-20. E: 73.X. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor unit)
- 2-21. E: 74.X. Outdoor temperature thermistor error (Outdoor unit)
- 2-22. E: 77.X. Heat sink thermistor error (Outdoor unit)
- 2-23. E: 84.X. Current sensor error (Outdoor unit)
- 2-24. E: 86.X. High pressure switch error (Outdoor unit)
- 2-25. E: 86.X. Pressure sensor error (Outdoor unit)
- 2-26. E: 94.X. Trip detection (Outdoor unit)
- 2-27. E: 95.X. Compressor motor control error (Outdoor unit)
- 2-28. E: 97.X. Outdoor unit fan motor error (Outdoor unit)
- 2-29. E: 99.X. 4-way valve error (Outdoor unit)
- 2-30. E: A1.X. Discharge temperature error (Outdoor unit)
- 2-31. E: A5.X. Low pressure error (Outdoor unit)
- 2-32. E: AC.X. Heat sink temperature error (Outdoor unit)
- 3. Troubleshooting without error code
- 4. Troubleshooting with error code (For wireless LAN adapter)
- 4-1. E: 18.X. External communication error between indoor unit and WLAN adapter
- 4-2. Wireless LAN adapter error
- 4-3. Network communication error between wireless LAN router and WLAN adapter
- 4-4. E: 18.X. Communication error
- 4-5. E: 18.X. Wireless LAN adapter non-energized
- 4-6. Wireless LAN adapter Sleep mode (Indoor unit)
- 4-7. Mobile app setting method
- 5. Service parts information
- 6. Thermistor resistance values
- 1. Error code
- 4. CONTROL AND FUNCTIONS
- 1. Rotation number control of compressor
- 2. Auto changeover operation
- 3. Fan control
- 4. Louver control
- 5. Timer operation control
- 6. Defrost operation control
- 7. Various control
- 7-1. Auto restart
- 7-2. MANUAL AUTO operation
- 7-3. Forced cooling operation
- 7-4. MIN. HEAT operation
- 7-5. ECONOMY operation
- 7-6. POWERFUL operation
- 7-7. Fresh air control
- 7-8. Compressor preheating
- 7-9. External electrical heater control
- 7-10. Electronic expansion valve control
- 7-11. Prevention to restart for 3 minutes (3 minutes st)
- 7-12. 4-way valve control
- 7-13. Peak cut operation
- 7-14. Unit status monitoring and the detected value indication
- 8. Various protections
- 5. FILED WORKING
- BACK COVER
2-30. E: A1.X. Discharge temperature error (Outdoor unit)
Indicator
Indoor unit
Operation indicator 10 time flash
Timer indicator 1 time flash
Economy indicator Continuous flash
Error code E: A1
outdoor unit Refer to "Error code table (Outdoor unit)" on page 03-4
Detective actuator
Outdoor unit main PCB Protection stop by discharge temperature ≥ 230 °F
(110 °C) during compressor operation generated 2 times
within 24 hours.
Discharge temperature thermistor
Forecast of cause
3-way valve not opened
EEV or capillary tube defective, strainer clogged
Outdoor unit operation failure, foreign matter on heat
exchanger
Discharge temperature thermistor failure
Insufficient refrigerant
Main PCB failure
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE: For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
Check point 2. Check any of the electronic expansion valve (EEV), capillary tube, or strainer, or all
• Check if EEV open or there is a capillary tube defect.
Refer to outdoor unit Electrronic Expansion Valve (EEV) or Capillary tube in "Service parts in-
formation" on page 03-80.
• Check the strainer clogging.
Check point 3. Check the outdoor unit fan and heat exchanger
• Check for foreign object at heat exchanger
• Check if fan can be rotated by hand.
• Check the motor. (Refer to outdoor unit fan motor in "Service parts information" on page 03-
80.)
Check point 4. Check the discharge thermistor
The discharge temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE: For the characteristics of the thermistor, refer to "Thermistor resistance values" on page
03-88.
2-30. E: A1.↓. Discharge temperature error (Outdoor unit) - (03-47) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING