LMAS Service Manual
Table Of Contents
- SERVICE MANUAL
- 1. GENERAL INFORMATION
- 2. TECHNICAL DATA AND PARTS LIST
- 3. TROUBLESHOOTING
- 1. Error code
- 1-1. How to check the error memory
- 1-2. How to erase the error memory
- 1-3. Error code table (Indoor unit and wired remote controller)
- 1-4. Error code table (Outdoor unit)
- 1-5. Error code table (Wireless LAN indicator)
- 1-6. Error code table (Mobile app)
- 1-7. Error message for wireless LAN control (Mobile app)
- 2. Troubleshooting with error code
- 2-1. E: 11.X. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- 2-2. E: 11.X. Serial communication error (Serial forward transfer error) (Indoor unit)
- 2-3. E: 12.X. Wired remote controller communication error (Indoor unit)
- 2-4. E: 18.X. External communication error (Indoor unit)
- 2-5. E: 23.X. Combination error (Outdoor unit)
- 2-6. E: 26.X. Address setting error in wired remote controller (Indoor unit)
- 2-7. E: 29.X. Connected unit number error (Indoor unit)
- 2-8. E: 32.X. Indoor unit main PCB error (Indoor unit)
- 2-9. E: 35.X. MANUAL AUTO button error (Indoor unit)
- 2-10. E: 3A.X. Indoor unit communication circuit error (Indoor unit)
- 2-11. E: 41.X. Room temperature sensor error (Indoor unit)
- 2-12. E: 42.X. Indoor unit heat exchanger sensor error (Indoor unit)
- 2-13. E: 51.X. Indoor unit fan motor error (Indoor unit)
- 2-14. E: 58.X. Intake grille error (Indoor unit)
- 2-15. E: 62.X. Outdoor unit main PCB error (Outdoor unit)
- 2-16. E: 63.X. Inverter error (Outdoor unit)
- 2-17. E: 64.X. PFC circuit error (Outdoor unit)
- 2-18. E: 65.X. Trip terminal L error (Outdoor unit)
- 2-19. E: 71.X. Discharge thermistor error (Outdoor unit)
- 2-20. E: 73.X. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor unit)
- 2-21. E: 74.X. Outdoor temperature thermistor error (Outdoor unit)
- 2-22. E: 77.X. Heat sink thermistor error (Outdoor unit)
- 2-23. E: 84.X. Current sensor error (Outdoor unit)
- 2-24. E: 86.X. High pressure switch error (Outdoor unit)
- 2-25. E: 86.X. Pressure sensor error (Outdoor unit)
- 2-26. E: 94.X. Trip detection (Outdoor unit)
- 2-27. E: 95.X. Compressor motor control error (Outdoor unit)
- 2-28. E: 97.X. Outdoor unit fan motor error (Outdoor unit)
- 2-29. E: 99.X. 4-way valve error (Outdoor unit)
- 2-30. E: A1.X. Discharge temperature error (Outdoor unit)
- 2-31. E: A5.X. Low pressure error (Outdoor unit)
- 2-32. E: AC.X. Heat sink temperature error (Outdoor unit)
- 3. Troubleshooting without error code
- 4. Troubleshooting with error code (For wireless LAN adapter)
- 4-1. E: 18.X. External communication error between indoor unit and WLAN adapter
- 4-2. Wireless LAN adapter error
- 4-3. Network communication error between wireless LAN router and WLAN adapter
- 4-4. E: 18.X. Communication error
- 4-5. E: 18.X. Wireless LAN adapter non-energized
- 4-6. Wireless LAN adapter Sleep mode (Indoor unit)
- 4-7. Mobile app setting method
- 5. Service parts information
- 6. Thermistor resistance values
- 1. Error code
- 4. CONTROL AND FUNCTIONS
- 1. Rotation number control of compressor
- 2. Auto changeover operation
- 3. Fan control
- 4. Louver control
- 5. Timer operation control
- 6. Defrost operation control
- 7. Various control
- 7-1. Auto restart
- 7-2. MANUAL AUTO operation
- 7-3. Forced cooling operation
- 7-4. MIN. HEAT operation
- 7-5. ECONOMY operation
- 7-6. POWERFUL operation
- 7-7. Fresh air control
- 7-8. Compressor preheating
- 7-9. External electrical heater control
- 7-10. Electronic expansion valve control
- 7-11. Prevention to restart for 3 minutes (3 minutes st)
- 7-12. 4-way valve control
- 7-13. Peak cut operation
- 7-14. Unit status monitoring and the detected value indication
- 8. Various protections
- 5. FILED WORKING
- BACK COVER
3-3. No operation (Power is on)
Forecast of cause
Setting/ Connection failure
External cause
Electrical components defective
Check point 1. Check indoor and outdoor installation condition
• Indoor unit:
– Check incorrect wiring between indoor unit and remote controller.
– Check if there is an open cable connection.
• Are these indoor unit, outdoor unit, and remote controller suitable model numbers to connect?
-> If there is some abnormal condition, correct it by referring to the installation manual and “DESIGN
& TECHNICAL MANUAL”.
Turn off the power and check correct followings.
• Is there loose or removed communication line of indoor unit and outdoor unit?
Check point 2. Check external cause at indoor and outdoor (Voltage drop or Noise)
• Instant drop: Check if there is a large load electric apparatus in the same circuit.
• Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
• Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point 3. Check wired remote controller and controller PCB
Check voltage at CN2 (terminal 1—3) of UT↔-T→R↓Z2 (Communication kit) (for 18
model). Check voltage at CN12 of main PCB (terminal 1—2) (for 24 model).
(Power supply to remote controller)
• If it is DC 5 V (for 18 model) and DC 12 V (for 24 model), remote controller is
failure. (The controller PCB is normal)
-> Replace remote controller.
• If it is DC 0 V, controller PCB is failure. (Check the remote controller once
again)
-> Replace controller PCB.
Check point 4. Replace main PCB
If check point 1 to 3 do not improve the symptom, change main PCB.
End
3-3. No operation (Power is on) - (03-54) - 3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING