Wall Mount Installation Manual

En-11
Control switching of external heaters
Sets the control method for the external heater being used. For details of the control method,
refer to the Design & Technical Manual.
(... Factory setting)
Function
number
Setting
value
Setting description
61
00 Auxiliary heater control 1
01 Auxiliary heater control 2
02 Heat pump prohibition control
03
Heater selection control using outdoor temperature 1
04
Heater selection control using outdoor temperature 2
05
Auxiliary heater control by outdoor temperature 3
06 Auxiliary heat pump control
07
Auxiliary heat pump control by outdoor temperature 1
08
Auxiliary heat pump control by outdoor temperature 2
09
Auxiliary heat pump control by outdoor temperature 3
Standby time for auxiliary equipment operation
Sets the standby time until the auxiliary equipment operation starts during primary equip-
ment operation.
(... Factory setting)
Function
number
Setting
value
Setting description
71
00 Disable
01 1 minutes
02 to 98 2 minutes to 98 minutes
99 99 minutes
Heat pump backup setting
Enables or disables the heat pump backup instruction from the outdoor unit.
This function will be usable provided that the corresponding outdoor unit is connected.
(... Factory setting)
Function
number
Setting
value
Setting description
72
00 Disable
01 Enable
Emergency heat for external output terminal
Enables or disables emergency heat input.
To use this function, select “External heater output” after entering “Function Number 60”. For
more information, refer to the Design & technical manual.
(... Factory setting)
Function
number
Setting
value
Setting description
73
00 Disable
01 Enable
Special cooling operation
It is used to stabilize cooling when the ambient temperature is low.
Operation mode : Fixed cooling
Air ow : Fixed Hi
Set temperature : 76°F (24°C) to 88°F (30°C)
(... Factory setting)
Function
number
Setting
value
Setting description
96
00 Disable
01 Enable
NOTES:
If setting value is set to “Enable”(01), connect the wired remote controller (optional).
Do not use the wireless remote controller after setting to “Enable”(01).
Cooling starts automatically after “Enable”(01) is set and the wired remote controller
cannot be communicated with.
If drops of water appear on the surface of the indoor unit after “Enable”(01) is set, set
setting value to “Disable”(00).
Setting record
Record any changes to the settings in the following table.
Function
number
Setting description Setting value
11 Filter sign
40 Auto restart
42 Room temperature sensor switching
44 Remote controller custom code
46 External input control
48 Room temperature sensor switching (Aux.)
49 Indoor unit fan control for energy saving for cooling
60 Switching functions for external output terminal
61 Control switching of external heaters
71 Standby time for auxiliary equipment operation
72 Heat pump backup setting
73 Emergency heat for external output terminal
96 Special cooling operation
After completing the Function Setting, be sure to disconnect the power supply and then recon-
nect it.
5.2. Temperature correction
NOTES:
When changing Function 95, perform this setting before other Room temp. control settings
(Function 30, 31, 35, 36).
If Function 95 is not set rst, Room temperature control settings (Function 30, 31, 35, 36)
will be reset and you must re-do them again.
Heat Insulation condition (building insulation)
Heat insulation conditions di er according to the installed environment.
“Standard insulation” (00) allows system to rapidly respond to the cooling or heating load
changes.
“High insulation” (01) is when the heat insulation structure of the building is high and does
not require system to rapidly respond to cooling or heating load changes.
When “High insulation” (01) is selected;
Overheating (overcooling) is prevented at the start-up.
All room temp. control settings (Function 30, 31, 35, 36) will reset to “No correction” [0.0°F
(0.0°C)].
(... Factory setting)
Function
number
Setting
value
Setting description
95
00 Standard insulation
01 High insulation
Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of room temp. sensor - correction temp. value
Example of correction :
When the temperature of room temp. sensor is 78 °F and the setting value is
“03” (-2 °F), the corrected temp. will be 80 °F (78 °F [-2 °F]).
The temperature correction values show the di erence from the “Standard setting” (00)
(manufacturer’s recommended value).
(... Factory setting)
Function number
Setting
value
Setting description
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0 °F (0.0 °C)
02 -1 °F ( -0.5 °C)
More
Cooling
Less
Heating
03 -2 °F (-1.0 °C)
04 -3 °F (-1.5 °C)
05 -4 °F (-2.0 °C)
06 -5 °F (-2.5 °C)
07 -6 °F (-3.0 °C)
08 -7 °F (-3.5 °C)
09 -8 °F (-4.0 °C)
10 +1 °F (+0.5 °C)
Less
Cooling
More
Heating
11 +2 °F (+1.0 °C)
12 +3 °F (+1.5 °C)
13 +4 °F (+2.0 °C)
14 +5 °F (+2.5 °C)
15 +6 °F (+3.0 °C)
16 +7 °F (+3.5 °C)
17 +8 °F (+4.0 °C)
9387603163-02_IM.indb 119387603163-02_IM.indb 11 6/30/2021 10:09:30 AM6/30/2021 10:09:30 AM