Wall Mount Installation Manual
En-8
3.5.2. Remote controller custom setting
Use the following steps to select the custom code of the remote controller. (Note that the
air conditioner cannot receive a signal if the air conditioner has not been set for the match-
ing custom code.)
(1) Press [START/STOP (
)] until only the clock is dis-
played on the remote controller display.
(2) Press [MODE] for at least 5 seconds to display the cur-
rent custom code (initially set to A).
(3) Press [TEMP. (
/ )] to change the custom code
between
A↔B↔C↔D
.
Match the code on the display to the air conditioner
custom code.
(4) Press [MODE] again to return to the clock display. The
custom code will be changed.
• If no buttons are pressed within 30 seconds after the custom code is displayed, the
system returns to the original clock display. In this case, start again from step 1.
• The air conditioner custom code is set to A prior to shipment.
4. OPTIONAL INSTALLATION WORK
CAUTION
• Before installing, be sure to disconnect all power supply.
• Do not touch the heat exchanger.
• When installing or removing parts of the air conditioner, be sure that the wire is not
caught by any parts or pulled hard. It may result in damage or malfunction of the air
conditioner.
• Connect the cable the circuit board.
CN13
CN65
CN46
CN47
This air conditioner can be connected with the following optional kits. To install these op-
tional kits, the optional External input and output PCB box is necessary.
For details on how to install optional parts, refer to the installation manual included in
each item.
Connector No. Option type
CN13
Wired remote controller (via the Communication kit)
Simple remote controller (via the Communication kit)
CN46 External input
CN47 External output
CN65 External input and output PCB
4.1. Optional kit installation
NOTES:
•
When some wired remote controller is connected, the wireless remote controller
cannot be used.
4.1.1. Installing the WLAN adapter
For installing the WLAN adapter, refer to the operation manual.
WLAN adapter cover
WLAN adapter
1. Open
2. Insert
4.1.2. External input and output
■
External input
• Indoor unit functions such as Operation/Stop or Forced stop can be done by using
indoor unit terminals.
• “Operation/Stop” mode or “Forced stop” mode can be selected with function setting of
indoor unit.
•
A twisted pair cable (22 AWG) should be used. Maximum length of cable is 492 ft. (150 m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
● Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal.
*1
PCB
Connector
(CN46)
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
Operation behavior
● Input signal type
Edge
ON
OFF
● When function setting is “Operation/Stop” mode 1.
Input signal Command
OFF → ON Operation
ON → OFF Stop
● When function setting is “Forced stop” mode.
Input signal Command
OFF → ON Forced stop
ON → OFF Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
● When function setting is “Operation/Stop” mode 2.
Input signal Command
OFF → ON Operation
ON → OFF Stop (R.C. disabled)
NOTE: For details, refer to “
■ External input control” in “5.1. Function details”.
■
External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft. (25 m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
● When interlocking with external device
Connector
(CN47)
PCB
Connected
device
Relay (Locally purchased)
or
● When displaying “Operation/Stop”
Connector
(CN47)
PCB
Connected device
Resistor
LED
Operation behavior
*If function setting “60” is set to “00”, refer to “5. FUNCTION SETTING”.