User Guide

Series HMI Connection Manual
V1.02 Revision January, 2012 203
Siemens S7 300 (ISO TCP)
HMI Factory Setting:
IP Address: 192.168.0.1
COM Port: 102
Control Area / Status Area: DBW0 / DBW20
Connection
Standard Jumper Cable / Network Cable without jumper (Auto-detected by HMI)
Definition of PLC Read/Write Address
a. Registers
Format
Type
Word No.(n)
Bank No.(m)
Read/Write Range Data Length Note
IWn IW0 – IW65534 Word
Input Image
IDn ID0 – ID65532 Double Word
QWn QW0 – QW65534 Word
Output Image
QDn QD0 – QD65532 Double Word
MWn MW0 – MW65534 Word
Internal Bits
MDn MD0 – MD65532 Double Word
DBm.DBWn DB1.DBW0 –
DB255.DBW65534
Word 1
Data Area
DBm.DBDn DB1.DBD0 –
DB255.DBW65532
Double Word
1
DBWn DBW0 – DBW65534 Word
DBDn DBD0 – DBD65532 Double Word
VWn VW0 – VW65534 Word
Data Area (DB10)
VDn VD0 – VD65532 Double Word
Timer Tn T0 – T65535 Word 2
Counter
Cn C0 – C65535 Double Word
3