Technical Manual

Table Of Contents
7. Safety devices
Type of
protection
Protection form
Model
ASUH30LPAS ASUH36LPAS
Circuit
protection
Current fuse (PCB*) 250 V, 3.15 A
Fan motor
protection
Thermal protection
Activate
257±18°F (125±10°C)
Fan motor stop
Reset
212±18°F (100±10°C)
Fan motor restart
*PCB: Printed Circuit Board
- 13 -
7. Safety devices
WALL MOUNTED
ASUH30-36LPAS
WALL MOUNTED
ASUH30-36LPAS