Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
Mode
Function
setting
Rotary
SW
External output
Indoor unit External input and output PCB
CN47
1
CN310
2
CN311
3
CN312
0-1 60-00 1 Operation/Stop Operation/Stop Error status
Indoor unit fan
operation status
0-2 60-00 2 Operation/Stop Error status
Indoor unit fan
operation status
External heater
output
1 60-01 3
Cooling
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
2 60-02 4
Cooling
thermostat On
Error status
Remote
controller output
External heater
output
3 60-03 5
Cooling
thermostat On
Cooling high/low
output
Remote
controller output
External heater
output
4 60-04 6
Cooling
thermostat On
Error status
Remote
controller output
Cooling high/low
output
5 60-05 7
Heating
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
6 60-06 8 Operation/Stop Error status
Indoor unit fan
operation status
Heating
thermostat On
7 60-07 9
Cooling
thermostat On
Error status
Heating
thermostat On
External heater
output
8 60-08 A
Cooling
thermostat On
Heating
thermostat On
Remote
controller output
External heater
output
9 60-09 B Error status Operation/Stop
Indoor unit fan
operation status
External heater
output
10 60-10 C
Indoor unit fan
operation status
Operation/Stop Error status
External heater
output
11 60-11 D
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
ยข
Input signal type
External input and output PCB:
The input signal type can be selected.
Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and out-
put PCB.
Pulse
The width of pulse must be
longer than 200 msec.
Edge
- 20 -
8-3. Combination of external input and output
8. External input and output
WALL MOUNTED
ASUH30-36LPAS
WALL MOUNTED
ASUH30-36LPAS