Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
10) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number Setting value Setting description Factory setting
60
00 Operation status ♦
01—04 Cooling thermostat On
05 Heating operation
06 Operation/Stop
07—08 Cooling thermostat On
09 Error status
10 Indoor unit fan operation status
11 External heater
12 Set point attainment status
11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to “External heater output” in Chapter 8-4. "Details of function" on page 21.
Function
number
Setting value Setting description
Factory
setting
61
00 Auxiliary heater control 1 ♦
01 Auxiliary heater control 2
02 Heat pump prohibition control
03 Auxiliary heater control by outdoor temperature 1
04 Auxiliary heater control by outdoor temperature 2
05 Auxiliary heater control by outdoor temperature 3
06 Auxiliary heat pump control
07 Auxiliary heat pump control by outdoor temperature 1
08 Auxiliary heat pump control by outdoor temperature 2
09 Auxiliary heat pump control by outdoor temperature 3
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to “External heater output” in Chapter 8-4. "Details of function" on page 21.
Function
number
Setting value
Setting description
Factory
setting
Heater: On Heater: Off
62
00 -5.4 °F (-3 °C) -1.8 °F (-1 °C) ♦
01 -3.6 °F (-2 °C) -1.8 °F (-1 °C)
02 -3.6 °F (-2 °C) -1.8 °F (-1 °C)
03 -5.4 °F (-3 °C) -1.8 °F (-1 °C)
04 -7.2 °F (-4 °C) -1.8 °F (-1 °C)
05 -9.0 °F (-5 °C) -1.8 °F (-1 °C)
- 53 -
11-1. Function settings by using remote controller
11. Function settings
WALL MOUNTED
ASUH30-36LPAS
WALL MOUNTED
ASUH30-36LPAS