Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
Multiple outdoor unit installation
• Provide at least 250 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side.
When 4 units or more are arranged in a line, provide the space as shown in the following ex-
ample “When an obstruction in the upper space:”.
• When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only. When there are obstacles at the front only.
12 (300)
or more
10 (250)
or more
60 (1,500)
or more
10 (250) or more
When there are obstacles at the front and
rear.
20 (500)
or more
60 (1,500)
or more
10 (250) or more
• When an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
60 (1,500) or more
20 (500) or more
10 (250)
or more
10 (250)
or more
Max. 11
(300)
60 (1,500)
or more
- 66 -
3-1. Models: AOUH30LPAS1 and AOUH36LPAS1
3. Installation space
OUTDOOR UNIT
AOUH30-36LPAS1
OUTDOOR UNIT
AOUH30-36LPAS1