Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Models: AOUH30LPAS1 and AOUH36LPAS1
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5 7.5 10 20 30 40 50
ft 16 24 32 65 98 131 164
Height difference H
Indoor unit is higher than outdoor
unit *1
30 98 - - - - 0.932 0.929 0.924
20 65 - - - 0.945 0.947 0.945 0.940
10 32 - - 0.984 0.961 0.963 0.960 0.956
7.5 24 - 0.988 0.988 0.965 0.967 0.964 0.959
5 16 0.992 0.992 0.992 0.968 0.971 0.968 0.963
0 0 0.998 1.000 1.000 0.976 0.979 0.976 0.971
Indoor unit is lower than outdoor
unit *2
-5 -16 0.998 1.000 1.000 0.976 0.979 0.976 0.971
-7.5 -24 - 1.000 1.000 0.976 0.979 0.976 0.971
-10 -32 - - 1.000 0.976 0.979 0.976 0.971
-20 -65 - - - 0.976 0.979 0.976 0.971
-30 -98 - - - - 0.979 0.976 0.971
HEATING
Pipe length
m
5 7.5 10 20 30 40 50
ft 16 24 32 65 98 131 164
Height difference H
Indoor unit is higher than outdoor
unit *1
30 98 - - - - 0.816 0.756 0.686
20 65 - - - 0.872 0.816 0.756 0.686
10 32 - - 0.991 0.872 0.816 0.756 0.686
7.5 24 - 1.000 0.991 0.872 0.816 0.756 0.686
5 16 0.986 1.000 0.991 0.872 0.816 0.756 0.686
0 0 0.986 1.000 0.991 0.872 0.816 0.756 0.686
Indoor unit is lower than outdoor
unit *2
-5 -16 0.981 0.995 0.986 0.868 0.812 0.752 0.683
-7.5 -24 - 0.993 0.983 0.866 0.810 0.750 0.681
-10 -32 - - 0.981 0.864 0.808 0.748 0.679
-20 -65 - - - 0.855 0.799 0.740 0.672
-30 -98 - - - - 0.791 0.733 0.665
- 70 -
6-1. Models: AOUH30LPAS1 and AOUH36LPAS1
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOUH30-36LPAS1
OUTDOOR UNIT