Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
10. Electrical characteristics
Model name AOUH30LPAS1 AOUH36LPAS1
Power supply
Voltage V 208/230
Frequency Hz 60
MCA *
1
A 23.4
Starting current A 13.4 17.8
Wiring spec.
*
2
MAX. CKT. BKR *
3
A 30
Power cable AWG 12
Connection
cable *
4
Size AWG 14
Limited wiring
length
ft (m) 167 (51)
*
1
: Minimum Circuit Ampacity (Calculation based on UL60335-2-40)
*
2
: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*
3
: Maximum Circuit Breaker
*
4
: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 75 -
10. Electrical characteristics
OUTDOOR UNIT
AOUH30-36LPAS1
OUTDOOR UNIT
AOUH30-36LPAS1