Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
12. External input and output
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
Connector Input Output Remarks
P580 Low noise mode —
See external input/output settings
for details.
PA580 Peak cut mode —
P590 — Error status
PA590 — Compressor status
12-1. External input
With using external input function, on/off status of “Low noise mode” and “Peak cut mode” can be
specified by the external signal.
¢
Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in nor-
mal operating condition:
The air conditioner is set to the “Low noise mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
NOTE: Product performance may drop depending on some conditions such as the outdoor temper-
ature.
• Circuit diagram example
Outdoor unit
control PCB
Connected unit
(Locally purchased)
Example: Switch
Signal
Connector
1
2
1
2
P580PA580
10m*
(33ft)
• Contact capacity: DC 24 V or more, 10 mA or
more.
• *: Make the distance from the PCB to the
connected unit within 33 ft (10 m).
• Construct a circuit as shown in this figure
with using optional parts mentioned below.
• Input signal: On in “Low noise mode”
• Input signal: Off in normal operation
• To set the level of “Low noise mode”, refer to
"Low noise mode" on page 83.
On
Off
On
Off
Input signal
Low noise mode
• Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
External input wire
- 77 -
12-1. External input
12. External input and output
OUTDOOR UNIT
AOUH30-36LPAS1
OUTDOOR UNIT
AOUH30-36LPAS1