Datasheet
ABY80/100/125Ui
103
102
ABY80Ui ABY100Ui ABY125Ui
7310 8600 10750
8500 10000 12500
8600 9288 12040
10000 10800 14000
2,83 2,43 2,81
3,45 3,31 3,29
230/1/50 230/1/50 230/1/50
3,0/2,90 4,12/3,26 4,45/4,25
10 10 15
13,1/12,7 18,0/14,2 19,5/18,5
(O.U.) 2x2,5+T (O.U.) 2x4+T (O.U.) 2x4+T
3x1,5+T 3x1,5+T 3x1,5+T
45 48 50
42 45 47
37 40 43
53 54 54
1660 1660 1660
700 700 700
240 240 240
900 900 900
330 330 330
830 830 1290
48/70 48/70 48/105
3/8”-5/8” 3/8”-5/8” 3/8”-5/8”
50/30 50/30 70/30
R410A R410A R410A
10 20 20
-10/ +43 -10/ +43 -15/ +43
-15/+24 -15/+24 -15/+24
ABY80-125Ui
ABY80/100Ui ABY125Ui
Models
Horizontal fan.
Air
Exterior
Air
Interior
Vertical fan.
Large ceiling
External fresh air contribution.
ABY80Ui ABY100Ui ABY125Ui
INVERTER HEAT PUMP INVERTER HEAT PUMP INVERTER HEAT PUMP
3NGF8340 3NGF8350 3NGF8360
ABY30LBAG ABY36LBAG ABY45LBAG
AOY30LMAWL AOY36LMAWL AOY45LJBYL
2.255 2.486 2.914
Code
Logistic reference indoor unit
Logistic reference outdoor unit
Price ref.
MODEL
Cooling capacity
kcal/h
W
Heating capacity kcal/h
W
Energy efficiency ratio (E.E.R.) Cooling
Heating
Power supply V/nº/Hz
Power consumption (Cooling/Heating) kW
Starting current A
Running current (Cooling/Heating) A
Electrical wiring
Electrical connection
Noise level indoor unit
High dB (A)
Medium dB (A)
Low dB (A)
Noise level outdoor unit dB (A)
Dimensions indoor unit Width mm
Depth mm
Height mm
Dimensions outdoor unit Width mm
Depth mm
Height mm
Net weight (Indoor U./Outdoor U.) kg
Pipe size Inch.
Piping lenght max. (Total/Height) m
Refrigerant type
Refrigerant charge m
Operating range Cooling ºC
Heating ºC
Twin auto swing:
that allows 5 selections for the vertical or horizontal airflow direction.
Outside fresh air contribution:
via a conduit with a diameter of 200 mm connected to the upper or
rear part of the machine. Air renewal is very useful in public premises
that hold a lot of people.
Optional drain water lifter:
an optional accessory that allows a level difference about 30 cm
in the false ceiling to be able to generate the necessary slope until it
reaches the nearest down pipe (see page 172).
Semi-insertable units:
these units are designed to fit into a plaster false ceiling with a mini-
mum height of 15 cm. This means only 14 cm of the machine will be
visible.