Datasheet
ABY80/100/125/140U/UT/F/FT
105
104
ABY80U ABY100UT ABY125UT ABY140UT ABY80F ABY100FT ABY125FT ABY140FT
7225 9030 10922 12470 7225 9030 10920 12470
8400 10500 12700 14500 8400 10500 12700 14500
8170 10150 12298 14190 —- —- —- —-
9500 11800 14300 16500 —- —- —- —-
2,85 3,02 2,90 2,81 2,85 2,84 2,90 2,81
3,42 3,42 3,26 3,11 —- —- —- —-
230/1/50 400/3/50 400/3/50 400/3/50 230/1/50 400/3/50 400/3/50 400/3/50
2,95/2,78 3,48/3,45 4,38/4,40 5,16/5,30 2,95/- 3,70/- 4,38/- 5,16/-
70 37 67 70 70 37 67 70
13,6/13,1 5,9/6,2 7,7/7,7 9,5/9,5 13,8/- 6,2/- 7,7/- 9,5/-
2x4+T 3x2,5+N+T 3x2,5+N+T 3x2,5+N+T 2x4+T 3x2,5+N+T 3x2,5+N+T 3x2,5+N+T
3x1,5+T 3x1,5+T 3x1,5+T 3x1,5+T 3x1,5+T 3x1,5+T 3x1,5+T 3x1,5+T
42 45 48 52 42 45 48 52
39 42 46 50 39 42 46 50
35 37 41 46 35 37 41 46
53 54 54 54 53 54 54 54
1660 1660 1660 1660 1660 1660 1660 1660
700 700 700 700 700 700 700 700
240 240 240 240 240 240 240 240
900 900 900 900 900 900 900 900
330 330 330 330 330 330 330 330
830 1165 1165 1290 830 1165 1165 1290
48/69 48/94 48/113 48/118 48/68 48/80 48/109 48/114
3/8”-5/8” 3/8”-5/8” 3/8” -3/4” 3/8” -3/4” 3/8”-5/8” 3/8”-5/8” 3/8”-3/4” 3/8”-3/4”
30/15 50/30 50/30 50/30 30/15 50/30 50/30 50/30
R410A R410A R410A R410A R410A R410A R410A R410A
7,5 20 20 20 7,5 20 20 20
0 / +43 0 / +43 0 / +43 0 / +43 0 / +43 0 / +43 0 / +43 0 / +43
-7/ +24 -10/ +24 -10/ +24 -10/ +24 - - - -
ABY80-140U/UT/F/FT
ABY100/125/140UT/FT
(mod. ABY_U/UT)
ABY80U/F
Models
ABY80U ABY100UT ABY125UT ABY140UT ABY80F ABY100FT ABY125FT ABY140FT
HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP COOLING ONLY COOLING ONLY COOLING ONLY COOLING ONLY
3NGF3245 3NGF3255 3NGF3275 3NGF3285 3NGF3045 3NGF3055 3NGF3075 3NGF3085
ABY30UBAG ABY36UBAG ABY45UBAG ABY54UBAG ABY30FBAG ABY36FBAG ABY45FBAG ABY54FBAG
AOY30UNBWL AOY36UNAXT AOY45UMAXT AOY54UMAYT AOY30FNBWL AOY36FNAXT AOY45FMAXT AOY54FMAYT
1.895 2.143 2.428 2.810 1.800 2.036 2.307 2.670
Code
Logistic reference indoor unit
Logistic reference outdoor unit
Price ref.
Large ceiling
FALSE CEILING
Vertical fan
Air flow direction.
Semi-insertable units in false ceilings.
Horizontal fan
MODEL
Cooling capacity
kcal/h
W
Heating capacity kcal/h
W
Energy efficiency ratio (E.E.R.) Cooling
Heating
Power supply V/nº/Hz
Power consumption (Cooling/Heating) kW
Starting current A
Running current (Cooling/Heating) A
Electrical wiring
Electrical connection
Noise level indoor unit
High dB (A)
Medium dB (A)
Low dB (A)
Noise level outdoor unit dB (A)
Dimensions indoor unit Width mm
Depth mm
Height mm
Dimensions outdoor unit Width mm
Depth mm
Height mm
Net weight (Indoor U./Outdoor U.) kg
Pipe size Inch.
Piping lenght max. (Total/Height) m
Refrigerant type
Refrigerant charge m
Operating range Cooling ºC
Heating ºC
Large air current:
ideal for large commercial premises, warehouses and offices with a
height of up to 4 m.
Outside fresh air contribution:
via a conduit with a diameter of 200 mm connected to the upper or
rear part of the machine. Air renewal is very useful in public premises
that hold a lot of people.
Optional drain water lifter:
an optional accessory that allows a level difference about 30 cm
in the false ceiling to be able to generate the necessary slope until it
reaches the nearest down pipe (see page 172).
Tec hnical specifications
Large ceiling cooling- heat pump
104-105 2/05/06 09:57 Página 104