Installation guide
En-6
6.6. Pipe connection
CAUTION
Tighten the flare nuts with a torque wrench using the specified tightening method.
Otherwise, the are nuts could break after a prolonged period, causing refrigerant to leak
and generate hazardous gas if the refrigerant comes into contact with a ame.
6.6.1. Flaring
Use special pipe cutter and are tool designed for R410A or R32 pipework.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert the are nut (always use the are nut attached to the indoor unit(s) and outdoor
unit or branch box respectively) onto the pipe and perform the are processing with a
are tool. Use the special R410A or R32 are tool, or the conventional are tool. Leak-
age of refrigerant may result if other are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Die
A
Pipe
B
L
Check if [L] is flared uniformly
and is not cracked or scratched.
Pipe outside diameter
[mm (in.)]
Dimension A [mm]
Dimension B [mm]
Flare tool for R32,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional are tools to are R32 pipes, the dimension A should be approx-
imately 0.5 mm more than indicated in the table (for aring with R32 are tools) to achieve
the specied aring. Use a thickness gauge to measure the dimension A.
Width across
flats
Pipe outside diameter [mm (in.)]
Width across flats
of Flare nut [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
6.6.2. Bending pipes
CAUTION
• To prevent breaking of the pipe, avoid sharp bends.
• If the pipe is bent repeatedly at the same place, it will break.
• The pipes are shaped by your hands. Be careful not to collapse them.
• Bend R70 mm or more with a pipe bender.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it difcult
to bend or stretch them anymore.
• Do not bend or stretch the pipes more than 3 times.
• When bending the pipe, do not bend it as
is. The pipe will be collapsed. In this case,
cut the insulating pipe with a sharp cutter
as shown on the right, and bend it after
exposing the pipe. After bending the pipe
as you want, be sure to put the heat insu-
lating pipe back on the pipe, and secure it
with tape.
Pipe
Insulating
Pipe
Cutter
Cut line
6.6.3. Flare connection
WARNING
The are connection shall not be performed indoors.
CAUTION
• Be sure to install the pipe against the port on the indoor unit correctly. If the center-
ing is improper, the are nut cannot be tightened smoothly. If the are nut is forced
to turn, the threads will be damaged.
• Do not remove the are nut from the indoor unit pipe until immediately before con-
necting the connection pipe.
• Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order
to tighten the are nut correctly.
• Tighten the are nuts with a torque wrench using the specied tightening method.
Otherwise, the are nuts could break after a prolonged period, causing refrigerant to
leak and generate hazardous gas if the refrigerant comes into contact with a ame.
• Connect the piping so that the control box cover can easily be removed for servic-
ing when necessary.
• In order to prevent water from leaking into the control box, make sure that the pip-
ing is well insulated.
When the flare nut is tightened properly by your hand, hold the body side coupling with a
wrench, then tighten with a torque wrench. (See the following table for the flare nut tighten-
ing torques.)
Tighten with 2 wrenches.
Holding wrench
Flare nut
Connection pipe
Torque wrench
Indoor unit pipe
(Body side)
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
Do not remove the cap from the connection pipe before connecting the pipe.
7. ELECTRICAL WIRING
WARNING
• Before connecting the wires, make sure the power supply is OFF.
• Every wire must be connected rmly.
• No wire should be allowed to touch refrigerant tubing, the compressor, or any mov-
ing part.
• Loose wiring may cause the terminal to overheat or result in unit malfunction. A re
hazard may also exist. Therefore, be sure all wiring is tightly connected.
• Connect wires to the matching numbers of terminals.
CAUTION
Be careful not to generate a spark as follows for using a ammable refrigerant.
• Do not remove the fuse while the power is on.
• Do not disconnect the wiring while the power is on.
• It is recommended to position the outlet connection in a high position. Place the
cords so that they do not get tangled.
7.1.
Wiring system diagram
Type 60245 IEC57
Cable size 1.5 mm
2
(Inter-unit)
Earth (Ground) line
OUTDOOR UNIT
Please connect to the
specied terminal.
INDOOR UNIT
TERMINAL
Power line
Control line