AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASUH30LPAS ASUH36LPAS OUTDOOR AOUH30LPAS1 AOUH36LPAS1 DR_AS144EF_01 2021.11.
Notices: • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks FGLair™ is trademark of Fujitsu General Limited in the United States, other countries or both. Google Play™ is trademark of Google Inc. App Store® is a service mark of Apple Inc., registered in the U.S. and other countries. Copyright © 2021 Fujitsu General Limited. All rights reserved.
CONTENTS Part 1. INDOOR UNIT...........................................................................1 1. Specifications................................................................................................2 2. Dimensions....................................................................................................4 2-1. Models: ASUH30LPAS and ASUH36LPAS .....................................................................4 3. Wiring diagrams ...............................................
CONTENTS (continued) Part 2. OUTDOOR UNIT.....................................................................61 1. Specifications..............................................................................................62 2. Dimensions..................................................................................................63 2-1. Models: AOUH30LPAS1 and AOUH36LPAS1 ..............................................................63 3. Installation space ..........................................
Part 1.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 1. Specifications Wall mounted Type Inverter heat pump Model name ASUH30LPAS Power supply Power supply intake Available voltage range Rated Cooling Min.—Max. Rated Capacity Heating Min.—Max. Heating (17 °F)*1 Cooling Input power Heating Heating (17 °F)*1 Cooling Heating Current EER Rated Max. Rated Min.—Max. Rated Min.—Max. Rated Max.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS Wall mounted Type Inverter heat pump Model name ASUH30LPAS ASUH36LPAS NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB (26.67°CDB) /67°FWB (19.44°CWB), and outdoor temperature of 95°FDB (35°CDB) / 75°FWB (23.9°CWB). – Heating: Indoor temperature of 70°FDB (21.11°CDB) /59°FWB (15.56°CWB), and outdoor temperature of 47°FDB (8.33°CDB) /43°FWB (6.11°CWB).
WALL MOUNTED ASUH30-36LPAS 2-1. Models: ASUH30LPAS and ASUH36LPAS Unit: in (mm) 45-1/4 (1,150) 13-6/16 (340) 19 (483) 11 (280) 21-7/16 (544) 22-1/16 (560) 45-1/4 (1,150) 20-1/2 (520) 13/16 (20) 20-1/2 (520) 3-9/16 (90) Outline of unit 2-1/2 (64) 10/16 (16) 13-6/16 (340) 1-15/16 (50) 1-15/16 (50) 0 ø8 2-6/16 (61) 2-1. Models: ASUH30LPAS and ASUH36LPAS 18-7/8 (479) 19-6/8 (502) -4- ø8 0 WALL MOUNTED ASUH30-36LPAS 2. Dimensions 4-1/4 (108) 7/16 (11) 2.
CAUTION Do not place any other electrical products or household belongings under the product. Condensation dripping from the product might get them wet, and may cause damage or malfunction to the property. 3-8/1 (80) or more 2-1/2 (63) or more Unit: in (mm) Outline of unit 1-15/16 (50) or more 1-15/16 (50) or more 2-3/4 (70) or more 5-1/2 (140) or more 59-1/16 (1,500) or more 2-1. Models: ASUH30LPAS and ASUH36LPAS -5- 2.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 3. Wiring diagrams 3-1. Models: ASUH30LPAS and ASUH36LPAS 3-1. Models: ASUH30LPAS and ASUH36LPAS -6- 3.
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: ASUH30LPAS AFR CFM 812 Indoor temperature °FDB °FWB Outdoor temperature °FDB 14 23 32 41 50 59 67 77 87 95 104 115 64 54 TC SHC kBtu 24.67 16.64 22.40 15.41 21.26 14.91 22.73 15.32 24.00 16.58 25.31 17.41 27.81 19.42 26.98 18.49 25.70 17.83 24.26 17.06 22.68 16.27 17.26 13.57 IP kW 1.18 1.57 1.74 1.65 1.56 1.38 1.
CFM WALL MOUNTED ASUH30-36LPAS AFR 812 Indoor temperature °FDB °FWB Outdoor temperature °FDB 14 23 32 41 50 59 67 77 87 95 104 115 64 54 TC SHC kBtu 24.67 17.19 22.40 15.90 21.26 15.36 22.73 15.84 24.00 17.09 25.31 18.05 30.60 22.03 29.68 21.00 28.27 20.23 26.69 18.16 24.95 18.43 18.99 15.31 IP kW 1.18 1.57 1.74 1.65 1.56 1.38 2.44 3.16 3.52 3.92 4.30 3.58 70 60 TC SHC kBtu 27.00 18.81 24.51 17.40 23.26 16.81 24.87 17.34 26.26 18.70 27.70 19.75 33.48 24.10 32.48 22.98 30.93 22.13 29.21 19.87 27.
WALL MOUNTED ASUH30-36LPAS NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: ASUH30LPAS AFR CFM 812 Outdoor temperature °FDB °FDB °FWB 5 14 23 32 41 47 50 59 68 75 3 12 19 28 37 43 47 50 59 64 60 TC kBtu 25.35 28.66 30.85 33.03 35.21 34.82 34.48 32.85 31.22 29.95 IP kW 3.75 3.91 3.78 3.66 3.53 3.02 2.67 2.35 2.03 1.85 °CDB °CWB -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 24.0 -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.0 15.6 IP kW 3.83 3.99 3.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 5. Fan performance 5-1. Air velocity distributions ¢ Models: ASUH30LPAS and ASUH36LPAS Fan speed HIGH Measuring conditions Operation mode FAN (ft) (m) 14 Unit: ft/s (m/s) 4 3 7 2 1 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 0 7 (2.0) 0 5 (1.5) 3 (1.0) 1 7 2 2 (0.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 5-2. Airflow ¢ Models: ASUH30LPAS and ASUH36LPAS Cooling Fan speed Airflow HIGH m3/h l/s CFM MED m3/h l/s CFM LOW m3/h l/s CFM QUIET m3/h l/s CFM 1,380 383 812 1,130 314 665 910 253 536 710 197 418 Heating Fan speed HIGH 5-2. Airflow Airflow m3/h l/s CFM MED m3/h l/s CFM LOW m3/h l/s CFM QUIET m3/h l/s CFM - 11 - 1,380 383 812 1,130 314 665 910 253 536 710 197 418 5.
WALL MOUNTED ASUH30-36LPAS 6-1. Noise level curve ¢ Models: ASUH30LPAS and ASUH36LPAS Cooling Heating 80 Octave band sound pressure level, dB: (0 dB=0.0002 µbar) 80 Octave band sound pressure level, dB: (0 dB=0.
Type of protection Circuit protection Fan motor protection Model Protection form ASUH30LPAS Current fuse (PCB*) Thermal protection ASUH36LPAS 250 V, 3.15 A 257±18°F (125±10°C) Fan motor stop 212±18°F (100±10°C) Fan motor restart Activate Reset *PCB: Printed Circuit Board - 13 - 7. Safety devices WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 7.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 8. External input and output External input and output PCB Indoor unit PCB CN65 (Ext. in/out PCB) CN47 (Ext. out) CN46 (Ext.
With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m). • The wire connection should be separate from the power cable line. ¢ Indoor unit Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select: Use either one of these types of connectors according to the application. (Both types of connectors cannot be used simultaneously.) – Dry contact In case of internal power supply, set the slide switch of SW301 to "NON VOL" side.
Use an external output cable with appropriate external dimension, depending on the number of cables to be installed. ¢ Indoor unit • • • • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). Output voltage: High DC 12 V ± 2 V, Low 0 V. Permissible current: 50 mA For details, refer to "Combination of external input and output" on page 19.
• • • • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). Output voltage: High DC 12 V±2 V, Low 0 V. Permissible current: 50 mA For details, refer to "Combination of external input and output" on page 19. • When indicator or other components are connected directly: Example: Rotary SW on External input and output PCB is set to “1”.
By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions.
Function setting Rotary SW Indoor unit CN47 1 CN310 2 CN311 0-1 60-00 1 Operation/Stop Operation/Stop Error status 0-2 60-00 2 Operation/Stop Error status 1 60-01 3 2 60-02 4 3 60-03 5 4 60-04 6 5 60-05 7 6 60-06 8 7 60-07 9 8 60-08 A 9 60-09 B 10 60-10 C 11 60-11 D Mode External input and output PCB Cooling thermostat On Cooling thermostat On Cooling thermostat On Cooling thermostat On Heating thermostat On Cooling high/low output Operation/Stop Error s
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 8-4.
Function setting Rotary SW on External input and output PCB 46-02 1 External input External input and output PCB Input signal Command Off → On On → Off Forced stop Normal CN313 On CN313 Off Forced stop Normal Indoor unit Operation Stop On Remote controller On On – In the case of “Pulse” input: Function setting Rotary SW on External input and output PCB 46-02 1 External input External input and output PCB Input signal Command Pulse Pulse Forced stop Normal CN313 CN314 On CN313 Off
Function setting Rotary SW on External input and output PCB 46-03 1 External input External input and output PCB CN313 Input signal Command Off → On Operation Stop (R.C. disabled) On → Off On CN313 Off Operation Indoor unit Stop (R.C. disabled) On Remote contoller Off On – In the case of “Pulse” input: Function setting Rotary SW on External input and output PCB 46-03 1 External input External input and output PCB Input signal Command CN313 Pulse CN314 Pulse Operation Stop (R.C.
Rotary SW on Function setting / External input and output PCB 60-00 60-09 60-10 60-11 60-12 / / / / / 2 B C D D External input External input and output PCB CN313 Input signal Command Off → On Thermostat off On → Off Normal operation Output signal Command Off → On On → Off Operation Stop Off → On Operation On → Off Stop On Off Input Compressor On Off Room temp. Set temp.
Rotary SW on Function setting / External input and output PCB 60-09 / B External output Output of indoor unit 60-00 / 2 60-00 60-09 60-10 60-11 60-12 / / / / / CN47 CN310 1 B C D D External input and output PCB CN311 CN312 Output signal Command Off → On On → Off Off → On On → Off Error Normal Error Normal Off → On Error On → Off Off → On On → Off Normal Error Normal Output signal Command Off → On On → Off Fan run Fan stop Off → On Fan run On → Off Fan stop Off → On On → Off Fan run
Rotary SW on Function setting / External input and output PCB 8-4. Details of function External output 60-11 / D Output of indoor unit CN47 60-00 / 2 60-09 / B 60-10 / C External input and output PCB CN312 - 26 - Output signal Command Off → On On → Off Heater on Heater off Off → On Heater on On → Off Heater off 8.
Function setting Control Auxiliary heater control 1 Auxiliary heater control 2 Heat pump prohibition control Auxiliary heater control by outdoor temperature 1 Auxiliary heater control by outdoor temperature 2 Auxiliary heater control by outdoor temperature 3 Auxiliary heat pump control Auxiliary heat pump control by outdoor temperature 1 Auxiliary heat pump control by outdoor temperature 2 Auxiliary heat pump control by outdoor temperature 3 Primary heater Auxiliary heater Indoor unit Wired R. C.
• Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. Auxiliary heater control 1 Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature.
This control selects heat pump or external heater according to the outdoor temperature. When outdoor temperature is high, the heating is performed by using heat pump only. Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS • Operation status 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition zone Outdoor temperature zone * Combination zone Heat pump only zone On Comp. On/Off Off 12 V Heater Fan 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS • Operation status 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition zone Outdoor temperature zone * Combination zone On Comp. On/Off Off 12 V Heater Fan 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature.
Heat pump only zone 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off Heater Fan On Off 12 V 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone. • Other than heating • Test run 8-4. Details of function - 35 - 8.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS Auxiliary heat pump control • External heater output Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode • Error occurred • Forced thermostat off – Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.5 °C) – Temperature of heater off: Set temperature (Ts) + 0.9 °F (+ 0.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS Auxiliary heat pump control by outdoor temperature 1 • External heater output Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode • Error occurred • Forced thermostat off – Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS • Operation status 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition zone Outdoor temperature zone * Combination zone On Comp. On/Off Off 12 V Heater Fan 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS Auxiliary heat pump control by outdoor temperature 2 • External heater output Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode • Error occurred • Forced thermostat off – Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.
Heat pump prohibition zone 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off Heater Fan On Off 12 V 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone. • Other than heating • Test run 8-4. Details of function - 40 - 8.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS Auxiliary heat pump control by outdoor temperature 3 • External heater output Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode • Error occurred • Forced thermostat off – Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS • Operation status Heat pump prohibition zone 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off Heater Fan On Off 12 V 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Indoor unit Situation Function setting External output Mode Heating thermostat on no. 60 Rotary SW 5 6 7 8 60-05 60-06 60-07 60-08 7 8 9 A Example of individual connection Heating thermostat on Indoor unit fan operation status CN47 CN312 CN311 CN310 Not used • Example of individual connection External output: Heating thermostat on Humidifier • Operation status The heating thermostat output for CNB01 (1-2 or 1-3 or 1- or 1-5) will be on when comp on or external heater on.
NOTE: Group control cannot be used together with Wireless LAN adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall-mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available. 1. Connect up to 16 indoor units in a system. I.U. I.U. B I.U. C D I.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 10. Remote controller 10-1. Wireless remote controller ¢ Overview a MODE button o • Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT). • Starts/ends the remote controller custom code (max. 4 types) change. b FAN SPEED button n a b c POWERFUL button c d SET button (Left/right airflow) m l d k j i e f h • Press the FAN SPEED button while the air conditioner is operating, to control fan speed.
Unit: in (mm) 6-3/8 (162) Top view 1-3/4 (45) 11/16 (17) Front view Size (H × W × D) Weight Side view in (mm) oz (g) 6-3/8 × 1-3/4 × 11/16 (162 × 45 × 17) 2.3 (65.5) (without batteries) Holder Unit: in (mm) Top view 3.9 75 Ø 3.9 (Hole) 6.4 Hole 1-15/16 (49.3) Front view Size (H × W × D) Weight 10-1. Wireless remote controller in (mm) oz (g) 1-1/16 (26.6) Side view 4-13/16 × 1-15/16 × 1-1/16 (122 × 49.3 × 26.6) 1 (23.5) - 46 - 10.
To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting procedure and the content of each function setting, select appropriate functions for your installation environment.
1. Press the TEMP./SELECT ( ) ( ) buttons to select the function number. To switch between the left and right digits, press the MODE button. Function number 2. Press the FAN SPEED button to proceed the setting value. To return the function number selection, press the FAN SPEED button again. 3. Press the TEMP./SELECT ( ) ( ) buttons to select the setting value. To switch between the left and right digits, press the MODE button. Setting value 4.
Each function setting listed in this section is adjustable in accordance with the installation environment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no.
NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp. = Temp. of the room temp. sensor - Correction temp. value Example of correction: When the temperature of the room temp.
NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to “Both“ (01). Ensure that the Thermo Sensor icon is displayed on the remote controller screen. *When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No correction 0.0 °C" (01).
Function number Setting value Setting description Factory setting A B C D ♦ 44 00 01 02 03 7) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description Factory setting Operation/Stop mode 1 (R.C. enabled) (Setting prohibited) Forced stop mode Operation/Stop mode 2 (R.C. disabled) ♦ 46 00 01 02 03 8) Room temperature sensor switching (Aux.
Function number Setting value Setting description Factory setting Operation status Cooling thermostat On Heating operation Operation/Stop Cooling thermostat On Error status Indoor unit fan operation status External heater Set point attainment status ♦ 60 00 01—04 05 06 07—08 09 10 11 12 11) Control switching of external heaters Sets the control method for external heater to be used. For details, refer to “External heater output” in Chapter 8-4. "Details of function" on page 21.
Function number Setting value Setting description Factory setting -4.0 °F (-20 °C) -0.4 °F (-18 °C) 3.2 °F (-16 °C) 6.8 °F (-14 °C) 10.4 °F (-12 °C) 14.0°F (-10 °C) 17.6 °F (-8 °C) 21.2 °F (-6 °C) 24.8 °F (-4 °C) ♦ 66 00 01 02 03 04 05 06 07 08 14) Outdoor temperature zone boundary temperature B Setting required if changing of the outdoor temperature setting for heat pump only zone is required when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit.
Function number Setting value Setting description Factory setting 72 00 01 Disable Enable ♦ 17) Emergency heat for external output terminal Enables or disables emergency heat input. Function number Setting value Setting description Factory setting 73 00 01 Disable Enable ♦ NOTE: When this function is used, IR receiver unit is necessary. 18) Heat insulation condition (building insulation) Heat insulation conditions differ according to the installed environment.
To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code. When 2 or more air conditioners are installed in a room, and the remote controller is operating an air conditioner other than the one you wish to set, change the custom code of the remote controller to operate only the air conditioner you wish to set.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 12. Accessories 12-1. Models: ASUH30LPAS and ASUH36LPAS Part name Exterior Q’ty Part name Exterior Q’ty Operating manual 1 Drain hose insulation 1 Installation manual 1 Cloth tape 1 Wall hook bracket 1 Tapping screw (large) 8 Remote controller 1 Tapping screw (small) 2 Battery 2 Air cleaning filters 1 Remote controller holder 1 Filter holder 2 12-1. Models: ASUH30LPAS and ASUH36LPAS - 57 - 12.
WALL MOUNTED ASUH30-36LPAS WALL MOUNTED ASUH30-36LPAS 13. Optional parts 13-1. Controllers Exterior Office Mode Custom Auto Cool Away Heat Part name Model name Fri 10:00AM Set Temp. Cool Heat 84°F 68°F 80°F 74°F Fan Auto Room Temp. 76°F Vacation Status Menu Wired remote controller UTY-RNRUZ* Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wire type: Non-polar 2-wire Optional communication kit is necessary for installation.
Exterior Part name External connect kit Summary UTY-XWZX Use to connect with various peripheral devices and air conditioner PCB. Required when external device is UTY-XWZXZ5 connected. External connect kit 13-2. Others Model name External input and output PCB UTY-XCSXZ2 Use to connect with external devices and air conditioner PCB. Optional External connect kit is necessary for installation. Communication kit UTY-TWRXZ2 Use to connect Non-polar 2-core wired remote controller.
13-2. Others - 60 - 13.
Part 2.
1. Specifications Type Inverter heat pump AOUH30LPAS1 Power supply Power supply intake Available voltage range Starting current Airflow rate Fan A Cooling Heating Type × Q'ty Motor output Sound pressure level *1 13.4 2,187 (3,715) 2,187 (3,715) CFM (m3/h) Cooling Heating Dimensions (H × W × D) 52 53 54 54 Main 1: 29-3/4 × 35-5/8 × 11/16 (756 × 905 × 18.19) Main 2: 29-3/4 × 35-5/8 × 11/16 (756 × 905 × 18.19) Main 1: 18 (1.45) Main 2: 18 (1.
2. Dimensions 5-5/8 (143) A 11-5/8 (296) Gas 13-15/16 (354) 3-way valve (Gas) 3-way valve (Liquid) 10-1/2 (266) Liquid 1-9/16 (40) 12-5/8 (320) 2-3/16 (55) Liquid 25-9/16 (650) 2-1/2 (64) Gas 5-13/16 (147) 1-1/4 (48) Liquid Top view Detail A Detail B 12-5/8 (320) 37 (940) 1-9/16 (40) 9/16 (14) 2-Ф7/8 (22) Cable port 2-Ф1/8 (28) Cable port 2-Ф7/8 (22) Cable port 2-Ф1/8 (28) Cable port Front view 5-1/2 (140) Side view C 5/8 (16) 2-1.
3. Installation space ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance. Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
• When an obstruction in the upper space: Unit: in (mm) When there are obstacles at the rear, sides, and above. Max. 19 (500) Max. 19 (500) 40 (1,000) or more 40 (1,000) or more 8 (200) or more 12 (300) or more 3-1. Models: AOUH30LPAS1 and AOUH36LPAS1 - 65 - 20 (500) or more 10 (250) or more 3. Installation space OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 When there are obstacles at the rear and above.
• Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following example “When an obstruction in the upper space:”. • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the front only.
Outdoor unit installation in multi-row Unit: in (mm) Multiple parallel unit arrangement 10 6 (150) or more 119 (3,000) or more 24 (600) or more 60 (1,500) or more 10 (25 (25 0) or mo re 20 (500) or more 0) or mo re 138 (3,500) or more 24 (600) or more 60 (1,500) or more 10 (250) or more 60 (1,500) or more 20 (500) or more NOTES: • If the space is larger than stated above, the condition will be the same as when there is no obstacle.
4.
5. Wiring diagrams OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 5-1. Models: AOUH30LPAS1 and AOUH36LPAS1 5-1. Models: AOUH30LPAS1 and AOUH36LPAS1 - 69 - 5.
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is lower than outdoor unit *2 Outdoor unit Indoor unit H OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 Indoor unit is higher than outdoor unit *1 H Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOUH30LPAS1 and AOUH36LPAS1 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
7. Additional charge calculation Refrigerant type Factory charge amount R410A 4 lb 10 oz 2,100 lb oz g ¢ Refrigerant charge Total pipe length Additional charge ft m lb oz g 7-1. Models: AOUH30LPAS1 and AOUH36LPAS1 65 or less 20 or less 0 0 99 30 14 oz 400 - 71 - 131 40 1 lb 12 oz 800 165 (Max.) 50 (Max.) 2 lb 10 oz 1,200 OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 7-1. Models: AOUH30LPAS1 and AOUH36LPAS1 0.43 oz/ft (40 g/m) 7.
8. Airflow Cooling OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 8-1. Models: AOUH30LPAS1 and AOUH36LPAS1 Airflow m3/h 3,715 1,032 2,187 l/s CFM Heating Airflow m3/h 3,715 1,032 2,187 l/s CFM 8-1. Models: AOUH30LPAS1 and AOUH36LPAS1 - 72 - 8.
9. Operation noise (sound pressure) Cooling Heating 80 Octave band sound pressure level, dB: (0 dB=0.0002 µbar) 80 Octave band sound pressure level, dB: (0 dB=0.
9-2. Sound level check point Rear Microphone OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 Microphone Airflow 40 in (1 m) Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. 9-2. Sound level check point - 74 - 9.
10. Electrical characteristics OUTDOOR UNIT AOUH30-36LPAS1 Voltage Power supply Frequency MCA *1 Starting current *3 Wiring spec. *2 MAX. CKT. BKR Power cable Size Connection Limited wiring cable *4 length V Hz A A A AWG AWG AOUH30LPAS1 208/230 60 23.4 13.4 ft (m) AOUH36LPAS1 17.8 30 12 14 167 (51) *1: Minimum Circuit Ampacity (Calculation based on UL60335-2-40) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
11. Safety devices Circuit protection Fan motor protection AOUH30LPAS1 Current fuse (Main PCB) Activate Thermal protection Thermal protection program (Compressor temp.) Compressor protection Model Protection form Thermal protection program (Discharge temp.) Thermal protection program (Outdoor temp.) (Only in COOL and DRY mode) Reset Activate Reset Activate Reset Activate Reset - 76 - AOUH36LPAS1 250 V, 30 A 250 V, 3.15 A 250 V, 10 A × 2 251.6 ±16.2°F (122 ±9°C) Fan motor stop 240.8 +18.0-16.
12. External input and output Input Output Remarks P580 PA580 P590 PA590 Low noise mode Peak cut mode — — — — Error status Compressor status See external input/output settings for details. 12-1. External input With using external input function, on/off status of “Low noise mode” and “Peak cut mode” can be specified by the external signal.
¢ Peak cut mode Example: Switch Connector 1 2 1 2 • Contact capacity: DC 24 V or more, 10 mA or more. • *: Make the distance from the PCB to the connected unit within 33 ft (10 m). • Construct a circuit as shown in this figure with using optional parts mentioned below. • Input signal: On in “Peak cut mode” • Input signal: Off in normal operation • To set the level of “Peak cut mode”, refer to "Peak cut mode" on page 84.
12-2. External output Signal on air conditioner error status is generated when a malfunction occurs. • Circuit diagram example Outdoor unit control PCB 1 2 1 On/ Off Example: Relay unit Connector 12 V On/ Off Connected unit (Locally purchased) 2 Example: Fan • Output voltage (Vcc): DC 12 V 50 mA or less • *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
¢ Compressor status output Signal on compressor operation status is generated when the compressor is running. 1 2 1 On/ Off Example: Relay unit Connector 12 V On/ Off Connected unit (Locally purchased) 2 Example: Fan • Output voltage (Vcc): DC 12 V 50 mA or less • *: Make the distance from the PCB to the connected unit within 33 ft (10 m). 10m* (33ft) Signal Compressor status Operation Stop Output signal On Off • Optional part 12-2.
13. Function settings Perform appropriate function setting locally according to the installation environment. CAUTION OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 NOTE: Incorrect settings can cause a product malfunction. • Before setting up the switch buttons, discharge the static electricity from your body. • Never touch the terminals or the patterns on the parts that are mounted on the PCB. 13-1.
¢ Switch buttons and the functions LED lamps (3) (4) (5) OUTDOOR UNIT AOUH30-36LPAS1 (2) OUTDOOR UNIT AOUH30-36LPAS1 (1) S134 S133 S132 S131 S130 Switch buttons LED lamp Function or operation method (1) POWER/MODE Green (2) ERROR (3) PUMP DOWN (L1) LOW NOISE MODE (4) (L2 and L3) PEAK CUT MODE (5) (L4, L5, and L6) Red Orange Orange Orange Lights on while power on. Local setting in outdoor unit or error code is displayed with blink. Blinks during error operation.
13-2. Local setting procedure NOTE: Before performing the function setting, be sure to stop the operation of the air conditioner. 1. 2. Press the MODE switch button (S134) for 3 seconds or more to switch to “Local setting mode”. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch button (S132). POWER MODE PUMP ERROR DOWN LOW NOISE (L1) (L2) PEAK CUT (L3) (L4) (L5) (L6) Blinks (9 times) Sign “ 3.
¢ Peak cut mode Press the MODE switch button (S134) for 3 seconds or more to switch to “Local setting mode”. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch button (S132). OUTDOOR UNIT AOUH30-36LPAS1 POWER MODE PUMP ERROR DOWN LOW NOISE (L1) (L2) PEAK CUT (L3) (L4) (L5) OUTDOOR UNIT AOUH30-36LPAS1 1. 2. (L6) Blinks (9 times) Sign “ 3. ”: Lights off Press the SELECT switch button (S133), and adjust the LED lamp as shown below.
14. Accessories Part name Exterior Q’ty Installation manual 1 Drain pipe 1 14-1. Models: AOUH30LPAS1 and AOUH36LPAS1 Part name Drain cap - 85 - Exterior Q’ty 3 14. Accessories OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 14-1.
15. Optional parts Part name External connect kit Model name Summary Use to operate the external input and UTY-XWZXZ3 output functions of outdoor unit. OUTDOOR UNIT AOUH30-36LPAS1 OUTDOOR UNIT AOUH30-36LPAS1 Exterior - 86 - 15.