AGU9RLF Installation Manual

En-5
The side panel L, R installation
(1) Firstly, t the top part of the side panel, and insert top and bottom hooks.
(2) 4 screws is attached.
(3) The intake grille is attached.
Rope
Side panel R
Rope
Intake
grille
Front panel
Mounting shaft
Front panel
Intake grille
Side panel L
Screw
[] mark
Side panel R
Base
Base
Side panel R
CAUTION
Install the SIDE PANEL L, R and INTAKE GRILLE securely. If installation is imperfect,
the SIDE PANEL L, R or INTAKE GRILLE may fall off and cause injury.
]1
6.4. Cutting the hole in the wall for the connecting piping
(1) Cut a 65 mm diameter hole in the wall at the position shown in the gure.
(2) Always align the center of the wall hole. If misaligned, water leakage will occur.
(3) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap
with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied in
the installation set.)
(4) For left piping and right piping, cut the hole a little lower so that drain water will ow
freely.
For RIGHT REAR or LEFT REAR piping
(The following gure is a front view of the indoor unit installation location.)
Unit: mm (in.)
FOR RIGHT
REAR PIPING
FOR LEFT
REAR PIPING
550 (21-10/16)
Ø65 (2-9/16)
Ø65 (2-9/16)
59 (2-5/16)
48 (1-
14/16)
59 (2-5/16)
For RIGHT or LEFT piping
FOR RIGHT
PIPING
FOR LEFT
PIPING
Unit: mm (in.)
56 (2-
3/16)
18 (11/
16)
54 (2-
2/16)
54 (2-
2/16)
56 (2-
3/16)
18 (11/
16)
For RIGHT BOTTOM or LEFT BOTTOM piping
FOR RIGHT
BOTTOM
PIPING
Unit: mm (in.)
FOR LEFT
BOTTOM
PIPING
50 (1-
15/16)
182 (7-3/16) 64 (2-8/16)
29 (1-
2/16)
29 (1-
2/16)
135 (5-
5/16)
5 (3/16) to
10 (6/16)
Fasten with
vinyl tape
Wall cap*
Wall pipe*
*Field supplied
(Inside)
Wall
(Outside)
WARNING
If the wall pipe is not used,
the wire interconnecting the
indoor and outdoor units may
touch metal and cause electric
leakage.
6.5. Forming piping
(1) Pass the refrigerant pipe through the piping hole to indoor side.
(2) Arrange the pipes according to the direction of piping.
Unit: mm (in.)
Rear piping Left piping
Center of
wall hole
130 (5-2/16)
Floor
280 (11-0/16)
245 (9-10/16)
Back wall
100 (3-15/16)
Back wall
690 (27-3/16)
Right piping
30 (1-3/16)
Back wall
6.6. Note on drain hose
CAUTION
Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.
When inserting, be sure not to attach any material besides water. If any other material
is attached, it will cause deterioration and water leakage.
After removing drain hose, be sure not to forget mounting drain cap.
Be sure to x the drain hose with tape to the bottom of piping.
Prevent drain water freezing under low temperature environment.
When installing indoor unit’s drain hose outdoors, necessary measure for frost
protection should be taken to prevent drain water freezing.
Under low temperature environment (when outdoor temperature under 0 °C (32 °F)),
after cooling operation is executed, water in the drain hose could be frozen.
Once drain water is frozen, the drain hose will be blocked and water leakage may
result at the indoor unit.