AOU18RLXFZ Installation Manual

En-7
(1) Detach the caps and plugs from the pipes.
(2) Center the pipe against the port on the outdoor unit, and then turn the À are nut
by hand.
To prevent gas leakage, coat the À are
surface with alkylbenzene oil (HAB).
Do not use mineral oil.
(3) Attach the connection pipe.
Flare nut
Connection pipe
(Liquid)
Connection pipe
(Gas)
Flare nut
3-way valve (Gas)
2-way valve
(Liquid)
(4) When the À are nut is tightened properly by your hand, use a torque wrench to
¿ nally tighten it.
Torque wrench
Holding spanner
Body side
CAUTION
Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to
tighten the À are nut correctly.
Outer panel may be distorted if fastened only with a wrench. Be sure to ¿ x the
elementary part with a holding wrench (spanner) and fasten with a torque wrench
(refer to below diagram). Do not apply force to the blank cap of the valve or hang a
wrench, etc., on the cap. If blank cap is broken, it may cause leakage of refrigerant.
Flare nut [mm (in.)] Tightening torque [N·m (lbf·ft)]
6.35 (1/4) dia. 16 to 18 (11.8 to 13.3)
9.52 (3/8) dia. 32 to 42 (23.6 to 31.0)
12.70 (1/2) dia. 49 to 61 (36.1 to 45.0)
15.88 (5/8) dia. 63 to 75 (46.5 to 55.3)
19.05 (3/4) dia. 90 to 110 (66.4 to 81.1)
How to use adapter (connection ports of outdoor unit)4. 1. 3.
When using the ADAPTER, be careful not to overtighten the nut, or the smaller pipe
may be damaged.
Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit
where the À are nut comes in.
Use appropriate wrenches to avoid damaging the connection thread by
overtightening the À are nut.
Apply wrenches on both of À are nut (local part), and ADAPTER to tighten them.
Adapter tightening torque
Adapter type [mm (in.)] Tightening torque [N·m (lbf·ft)]
ø12.7 (1/2) ĺ ø9.52 (3/8) 49 to 61 (36.1 to 45.0)
PIPE INSTALLATION - 14.
Flare connection (pipe connection)4. 1.
CAUTION
Do not use mineral oil on a À ared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.
While welding the pipes, be sure to blow dry nitrogen gas through them.
The maximum lengths of this product are shown in the table. If the units are further
apart than this, correct operation cannot be guaranteed.
Flaring
Use special pipe cutter and À are tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that the cuttings will not enter the pipe and remove
any burrs.
(3) Insert the À are nut (always use the À are nut attached to the indoor and outdoor
units respectively) onto the pipe and perform the À are processing with a À are tool.
Leakage of refrigerant may result if other À are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
L
Check if [L] is À ared uniformly
and is not cracked or scratched.
Pipe
A
B
Die
Pipe outside
diameter [mm (in.)]
Dimension A [mm (in.)]
Dimension B
0
- 0.4
[mm (in.)]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
(0 to 1/32)
9.1 (3/8)
9.52 (3/8)
13.2 (17/32)
12.70 (1/2) 16.6 (21/32)
15.88 (5/8) 19.7 (25/32)
19.05 (3/4) 24.0 (15/16)
When using conventional À are tools to À are R410A pipes, the dimension A should
be approximately 1/32 in. more than indicated in the table (for À aring with R410A
À are tools) to achieve the speci¿ ed À aring. Use a thickness gauge to measure the
dimension A.
Pipe outside
diameter
[mm (in.)]
Width across À ats
of Flare nut
[mm (in.)]
6.35 (1/4) 17 (11/16)
9.52 (3/8) 22 (7/8)
12.70 (1/2) 26 (1-1/32)
15.88 (5/8) 29 (1-5/32)
19.05 (3/4) 36 (1-13/32)
Width across À ats
Bending pipes4. 1. 1.
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
curvature of 100mm (4 in.) or more.
If the pipe is bent repeatedly at the same place, it will break.
If pipes are shaped by hand, be careful not to collapse them.
Do not bend the pipes at an angle of more than 90°.
When pipes are repeatedly bent or stretched, the material will harden, making it
dif¿ cult to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.
Pipe connection4. 1. 2.
CAUTION
Be sure to install the pipe against the port on the indoor unit and the outdoor unit
correctly. If the centering is improper, the À are nut cannot be tightened smoothly.
If the À are nut is forced to turn, the threads will be damaged.
Do not remove the À are nut from the outdoor unit pipe until immediately before
connecting the connection pipe.
After installing the piping, make sure that the connection pipes do not touch the
compressor or outer panel. If the pipes touch the compressor or outer panel, they will
vibrate and produce noise.
9374747146_IM.indb 7 19/11/2556 11:48:30