AOU45RLXFZ Installation Manual

En-3
2. 4. System con guration
Layout example for the indoor units and outdoor unit
Valve cover removal
· Remove the six mounting screws.
· Remove the valve cover.
2. 4. 1. Connectable indoor unit capacity type (Outdoor unit: 45 model)
A
B
C
D
E
H1
H1
H2
Power source
208/230 V ~ 60 Hz
Power supply
cable
Connection
cable
Refrigerant pipe
OUTDOOR UNIT
INDOOR UNITS
UNIT E
7-9
UNIT D
7-12
UNIT C
7-18
UNIT B
7-24
UNIT A
7-24
CAUTION
The total capacity of the indoor units connected must be between 34,000 and 54,000
BTU.
Connection patterns are restricted. Normal operation is not guaranteed if connected
pattern in the combination not listed below. The product may be damaged. Surely con-
nect in accordance with the combination in the following connection pattern.
• To install an indoor unit, refer to the installation manual included with the indoor unit.
Indoor unit connection pattern
Indoor unit
ABCDE
1 24,000 24,000 ―――
2 24,000 18,000 ―――
3 24,000 15,000 ―――
4 24,000 12,000 ―――
5 18,000 18,000 ―――
6 24,000 18,000 12,000 ――
7 24,000 18,000 9,000 ――
8 24,000 18,000 7,000 ――
9 24,000 15,000 15,000 ――
10 24,000 15,000 12,000 ――
11 24,000 15,000 9,000 ――
12 24,000 15,000 7,000 ――
13 24,000 12,000 12,000 ――
14 24,000 12,000 9,000 ――
15 24,000 12,000 7,000 ――
16 24,000 9,000 9,000 ――
17 24,000 9,000 7,000 ――
18 24,000 7,000 7,000 ――
19 18,000 18,000 18,000 ――
20 18,000 18,000 15,000 ――
Indoor unit
ABCDE
21 18,000 18,000 12,000 ――
22 18,000 18,000 9,000 ――
23 18,000 18,000 7,000 ――
24 18,000 15,000 15,000 ――
25 18,000 15,000 12,000 ――
26 18,000 15,000 9,000 ――
27 18,000 15,000 7,000 ――
28 18,000 12,000 12,000 ――
29 18,000 12,000 9,000 ――
30 18,000 12,000 7,000 ――
31 18,000 9,000 9,000 ――
32 18,000 9,000 7,000 ――
33 15,000 15,000 15,000 ――
34 15,000 15,000 12,000 ――
35 15,000 15,000 9,000 ――
36 15,000 15,000 7,000 ――
37 15,000 12,000 12,000 ――
38 15,000 12,000 9,000 ――
39 12,000 12,000 12,000 ――
40 24,000 15,000 7,000 7,000
41 24,000 12,000 9,000 9,000
42 24,000 12,000 9,000 7,000
43 24,000 12,000 7,000 7,000
44 24,000 9,000 9,000 9,000
45 24,000 9,000 9,000 7,000
46 24,000 9,000 7,000 7,000
47 24,000 7,000 7,000 7,000
48 18,000 18,000 9,000 9,000
49 18,000 18,000 9,000 7,000
50 18,000 18,000 7,000 7,000
51 18,000 15,000 12,000 9,000
52 18,000 15,000 12,000 7,000
53 18,000 15,000 9,000 9,000
54 18,000 15,000 9,000 7,000
55 18,000 15,000 7,000 7,000
56 18,000 12,000 12,000 12,000
57 18,000 12,000 12,000 9,000
58 18,000 12,000 12,000 7,000
59 18,000 12,000 9,000 9,000
60 18,000 12,000 9,000 7,000
61 18,000 12,000 7,000 7,000
62 18,000 9,000 9,000 9,000
63 18,000 9,000 9,000 7,000
64 18,000 9,000 7,000 7,000
65 18,000 7,000 7,000 7,000
66 15,000 15,000 15,000 9,000
67 15,000 15,000 15,000 7,000
68 15,000 15,000 12,000 12,000
69 15,000 15,000 12,000 9,000
70 15,000 15,000 12,000 7,000
71 15,000 15,000 9,000 9,000
72 15,000 15,000 9,000 7,000
73 15,000 15,000 7,000 7,000
74 15,000 12,000 12,000 12,000
75 15,000 12,000 12,000 9,000
76 15,000 12,000 12,000 7,000
77 15,000 12,000 9,000 9,000
78 15,000 12,000 9,000 7,000
79 15,000 12,000 7,000 7,000
80 15,000 9,000 9,000 9,000
81 15,000 9,000 9,000 7,000
82 15,000 9,000 7,000 7,000
83 15,000 7,000 7,000 7,000
84 12,000 12,000 12,000 12,000
85 12,000 12,000 12,000 9,000
86 12,000 12,000 12,000 7,000
87 12,000 12,000 9,000 9,000
88 12,000 12,000 9,000 7,000
89 12,000 12,000 7,000 7,000
90 12,000 9,000 9,000 9,000
91 12,000 9,000 9,000 7,000
92 12,000 9,000 7,000 7,000
93 9,000 9,000 9,000 9,000
94 9,000 9,000 9,000 7,000
95 24,000 9,000 7,000 7,000 7,000
96 24,000 7,000 7,000 7,000 7,000
97 18,000 15,000 7,000 7,000 7,000
98 18,000 12,000 9,000 7,000 7,000
99 18,000 12,000 7,000 7,000 7,000
100 18,000 9,000 9,000 9,000 9,000
101 18,000 9,000 9,000 9,000 7,000
9380545101-06_IM_3L.indb 39380545101-06_IM_3L.indb 3 2018/6/20 14:01:522018/6/20 14:01:52