Server User Manual

XSCF>
diagxbu -y -b 00 -t 01
XSCF>
showlogs error
Note -
In the case of a dual power feed, connect the power cords in their original positions by
referring to the record that you made before the start of maintenance.
physical partition into which the chassis is incorporated is powered off.
The example below specifies the following:
00: BB-ID of the chassis to start the diagnosis
01: BB-ID of the destination where the chassis to start the diagnosis is connected
(You can specify one or more of these.)
To specify multiple connection destination BB-IDs, enter a command like
"diagxbu -y -b 00 -t 01 -t 02".
4.
Execute the showlogs command to confirm that the system is operating
normally.
For details, see "3.3.5 Checking log information."
5.
Pow er on the physical partition requiring maintenance.
For details, see "6.3 Powering On the Physical Partition Requiring Maintenance."
6.
Close the rack door.
15.6.3 System-stopped maintenance
1.
Connect all the power cords to the PSU backplane unit.
For details, see "6.5.1 Installing the power cord."
2.
Return to the operation of the XSCF firmware replacefru command to confirm
that the chassis has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
For a single-chassis configuration, you do not have to incorporate the chassis.
Proceed to step 5.
3.
Execute the diagxbu command to diagnose the crossbar cables.
Diagnosis is performed when the system board of the chassis connected with the
crossbar cables is not incorporated into the physical partition, or when the
physical partition into which the chassis is incorporated is powered off.
The example below specifies the following:
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
December 2013294