FSC PRIMECENTER Rack Status 2007-09-26
Within the basic units of PRIMECENTER racks, are no power outlets integrated.
It is possible to order such power outlets as follows (1- or 3- phase power outlet), or the connections to the
mains can be done via an UPS. In case there is no 16A CEE plug choosen (1-phase solutions is with an 16A CEE plug,
while it is choosable with the 3-phase solution), the connection to the mains (line) has to be done
as an fix connectionfrom an certified electrician according to the existing regulations.
The maximum current load for each phase may not exceed 16amp (with fixed connection, CEE and safety socket),
for each Euro socket connector may 10A not be exceeded.
3-phase power socket outlet 3~240 volt / 16 A
I
S26361-F2262-E31
3-phase permanent connection
with 3x8 (24) IEC320 C13 socjekts
12x dual pairs,
different colours per phase
+ 4m cable with 16A CEE (IEC 309)
red plug
1-phase power socket outlet 1~240 volt / 16A
II
S26361-F2262-E40 S26361-F2262-E41 SNP:SY-F1903E2-P
1-phase connection with 10 1-phase permanent connection Multiple socket outlet 4x peripherals +
Euro socket connectors, 4m with 10x IEC320 C13 Euro socket 1 x safety plug as extension, with
cable connected with 16A connectors, 4m cable with NEMA safety plug at the connection
CEE 1-phase plug blue colour
L6-30 plug only for USA / CAN
cable (3m in length)
max. 2x per rack *)
III
*) Consider the power rating!
Extension of the 1/3 phase connection possibilities
SNP:SY-F1903E1-P SNP:SY-F1903E2-P Order numbers for
Expansion 3 safety sockets (D) Multiple socket outlet 4x peripherals + bulk delivery
as extension, with 10A Euro socket 1 x safety plug as extension, with S26361-F2262-L31
connector at the connection cable safety plug at the connection S26361-F2262-L40
(1,5m in length) cable (3m in length) S26361-F2262-L41
1x per phase of the socket strip I + II 1x per phase of the socket strip I
SNP:SY-F1903L1-P
SNP:SY-F1903L2-P
Max. number of socket strips:
S26361-F2262-E31 S26361-F2262-E40 SNP:SY-F1903E2-P
max. per rack S26361-F2262-E45 max. per rack
4x 46 U rack max. per rack the Inrush current must
3x 38 U rack 6x 46 U rack not be more than 3,5mA
2x 24 U rack 5x 38 U rack 2x 46 U rack
3x 24 U rack 2x 38 U rack
2x 12 U rack 2x 24 U rack
2x 12 U rack