Service Manual

Compressor Thermistor Error
DC
Compressor temperature thermistor
Compressor temperature thermistor short detected
Compressor thermistor open detected
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
OK
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 14".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN62:3-4) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Compressor temperature thermistor (CN62:3-4)
Indoor Unit : Operation LED 7 times Flash, Timer LED 2 Times Flash,
Economy LED Continuous Flash.
Outdoor Unit : E. 72. 1
Error Code : 72
If the voltage does not appear, replace Main PCB
, and execute
the check operation again.
02-35
Trouble shooting 18
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
CN62
THERMISTOR
(COMP SHELL1)
THERMISTOR
(DIS.TEMP.1)
BLACK
BLACK
BLACK
BLACK
1234
1234