AGM Sealed 6V 415Ah Manual

www.FullriverbaTTery.com Page 11
4.4.1 - CURRENT
All Models (excl. FSG): The recommendedbulkcurrentis20-25%ofthe20HrAH
capacityor0.20xC20(20Hr.capacityinAH).Themaximum allowable bulk current is
35%ofthe20Hr.AHcapacityor0.35xC20(20Hr.capacityinAH),unlessspecied.
Example:
DC115-12 is rated at 115AH @ 20 Hrs.
The recommended bulk current is 0.20 x 115 = 23 Amps
The maximum bulk current is 0.35 x 115 = 40 Amps
FSG Series: The recommendedbulkcurrentis12.5%ofthe10Hr.AHcapacityor
0.125xC10(10Hr.capacityinAH).Themaximumallowablebulkcurrentis15%of
the10Hr.AHcapacityor0.15xC10(10Hr.capacityinAH),unlessotherwisestated.
Example:
FSG1660-2 is rated at 1110AH @ 10 Hrs.
The recommended bulk current is 0.125 x 1110 = 139 Amps
The maximum bulk current is 0.15 x 1110 = 167 Amps
4.4.2 - VOLTAGE SETTINGS (BOLD IS RECOMMENDED SETTING)
4.4.3 - TEMPERATURE SETTINGS
If you have a programmable charger or inverter that has a temperature
compensationsetting,itshouldbesetto-4mV/°C/cellor-2mV/°F/cell.TABLE
8 below has the temperature compensation voltage values for a 12V battery. For a
24V, 36V or 48V system, multiply the values in the table by 2, 3 or 4 respectively.
Charging
TABLE 6
Bulk
Absorption
Float
Charge State
14.4-14.7 V
14.4-14.7 V
13.6-13.7 V
12 Volt AGM
19.2-19.6 V
19.2-19.6 V
18.2 V
16 Volt AGM
28.8-29.4 V
28.8-29.4 V
27.2-27.4 V
24 Volt AGM
57.6-58.8 V
57.6-58.8 V
54.4-54.8 V
48 Volt AGM
Bulk
Absorption
Float
Charge Stage
15.30 V
15.30 V
14.25 V
32°F (0°C)
15.06 V
15.06 V
14.01 V
50°F (10°C)
14.82 V
14.82 V
13.77 V
68°F (20°C)
14.70 V
14.70 V
13.65 V
77°F (25°C)
14.58 V
14.58 V
13.53 V
86°F (30°C)
14.34 V
14.34 V
13.29 V
104°F (40°C)
TABLE 8
TABLE 7
Bulk
Absorption
Float
Charge State
14.4-14.7 V
14.4-14.7 V
13.6 V
12 Volt FSG
28.8-29.4 V
28.8-29.4 V
27.2 V
24 Volt FSG
57.6-58.8 V
57.6-58.8 V
54.6 V
48 Volt FSG
14.1-14.4 V
14.1-14.2 V
13.6 V
12 Volt DCG