AGMandGelbatterieshaveamuchlongershelflifethanwet,lead-acidbatteries.
Withaself-dischargeofonly1-3%permonth,AGMandGelbatteriescanbestored
forayearorlongerwithoutneedingtobecharged.
5.1 - BATTERY STORAGE PROCEDURE
1. Chargebatteriesbeforetheyareplacedinstorage.
2. Disconnectbatteriesfromtheequipmentandchargertoeliminateany
parasiticloads.
3. CheckthebatteriesbasedonconditionsandscheduleinTABLE 9 below.
4. Check the open circuit voltage (OCV) of each battery in the set. If any battery
within the set is less than the values in TABLE 10 below, recharge the battery
set.
5. Ifthechargerhasamaintenancemode,selectthatmodetoboostcharge
batteries. Otherwise, run the normal charge cycle.
6. IfthebatteriesarestoredshorterthanthetimeperiodsinTABLE 9,theydo
notneedtoberechargedpriortobeingputbackintoservice.
AGMandGelbatteriesdonothaveamemoryeect;sothereisnoneed
tofullydischargebatteriespriortocharging.
Storage
9 months
6 months
3 months
Time
Below 68°F (20°C)
68°F to 86°F (20°C to 30°C)
Above 86°F (30°C)
Temperature
TABLE 9
< 2.0 Volts
< 6.2 Volts
< 8.3 Volts
< 12.5 Volts
< 16.7 Volts
Open Circuit Voltage (O.C.V.)
2 Volt
6 Volt
8 Volt
12 Volt
16 Volt
Battery Nominal Voltage
TABLE 10