7.3.2 - ABSORPTION SETTINGS
AbsorptiontimevariesperinstallationaccordingtototalbanksizeandtotalPVkW.
Ourmaximumabsorptiontimeis4hours,howevermostinstallationsneed2-3
hours on average. To estimate your rough absorption time, use the following formu-
la:
[(AH * DOD) / CHARGE AMPS * 0.85]
IfyourchargecontrolleroersasettingsuchasAbsorbEndAmps(Outback)orsim-
ilarthatautomaticallytransferstooatchargebasedonampsaccepted,absorption
timeshouldbesetto4hoursandthissettingshouldbesettoapproximately1.75%
of total bank capacity in Ah.
7.3.3 - CHARGE RATE & EQUALIZATION
Chargeampsshouldbesetupto25%oftotalbankcapacityinAh.Theminimum
recommendedis10%,butverifythatyourabsorptiontimewillnotexceed4hours.
Equalizationisnotrecommendedforanyofourproducts,pleasedisableequaliza-
tionorsettotheminimumtimeandvoltageequaltoabsorb.Ifyouexperiencea
signicantlossincapacity,pleasecontactourtechnicalsupportforfurthersupport.
7.3.4 - DEFAULT SETTINGS
When custom settings are not available, please use the following options:
7.3.5 - INVERTER SETTINGS
LowVoltageCutOorLowBatteryCutOut(LVCO/LBCO)willvarybasedonhow
largeyourloadsareandmayrequireadjustmentifyourruntimeistooshort.
Ifyouhaveachargecontrollersettingnotlistedabove,youmaycallourtechnical
supportat(800)522-8191withyourchargecontroller’smake/modelandoursta
will assist you further.
Your Clean-Green Energy Solution
TABLE 13
MagnumEnergy
MidniteSolar
Schneider/Xantrex
Manufacturer
AGM 2
Switch 1-2: OFF/OFF, Switch 5-8: OFF/ON/ON/OFF
AGM
Setting(s)
TABLE 14
25%
50%
80%
Depth of Discharge
12.5 V
12.2 V
11.8 V
12 Volt
25.0 V
24.4 V
23.6 V
24 Volt
50.0 V
48.8 V
47.2 V
48 Volt