SECTION 2 EDR-IOM-2014-0318 INSTALLATION
2-13
TABLE 3 NOMINAL PIPE SIZE
Nominal
Pipe Size
ID Equivalent Pipe Length Max Capacity in ft3 of natural gas per hour. Pressure drop of
0.5”wc/Equivalent length of pipe (feet)
Inch (mm) Inch (mm) 90 Elb
Feet
(meter)
Tee
Feet
(meter)
20 40 60 80 100 150 200
1-1/4 (31.75) 1.380 (35.05) 3.45 (1.05) 6.9 (2.10) 950 ----- ----- ----- ----- ----- -----
1-1/2 (38.1) 1.610 (40.89) 4.02 (1.22) 8.04 (2.45) 1460 990 810 ----- ----- ----- -----
2 (50.8) 2.067 (52.50) 5.17 (1.57) 10.3 (3.13) 2750 1900 1520 1300 1150 950 800
2-1/2 (63.5) 2.469 (62.71) 6.16 (1.87) 12.3 (3.74) 4350 3000 2400 2050 1850 1500 1280
3 (76.2) 3.068 (77.92) 7.67 (2.33) 15.3 (4.66) 7700 5300 4300 3700 3250 2650 2280
4 (101.6) 4.026 (102.26) 10.10 (3.07) 20.2 (6.15) 15800 10900 8800 7500 6700 5500 4600
6 (152.4) 6.07 (154.17) 10.10 (3.07) 23.60 (7.19) ----- ----- ----- ----- 20200 16503 12766
8 (203.2) 7.98 (202.69) 13.30 (4.05) 29.10 (8.86) ----- ----- ----- ----- 41200 33660 29128
FIGURE 5 FULTON PH NEUTRALIZING KIT WITHOUT PUMP