Pressure Gauges
The range in which readings are expected to fall should comprise mid-scale on
the pressure gauge chosen (See Figure 12). Pressure gauges must be able to
withstand overpressure equal to the rating of the safety relief valves, normally
100 psig.
Thermometers
Thermometers should read up to 650°F (343°C). For systems with higher
operating temperatures, select thermometers accordingly.